Application
Point Database Application 2927
34
Siemens Industry, Inc.
Application Note, App 2927
140-1311
2015-07-07
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
96
CAL TIMER
12
HRS
1
0
--
--
97
SUPDUCT AREA
1.0
(0.09292)
SQ. FT (SQ
M)
0.025
(0.002323)
0
--
--
98
LOOP TIME
5
SEC
1
0
--
--
{99}
ERROR STATUS
0
--
1
0
--
--
104
SENSOR SEL
8
--
1
0
--
--
106
MODHTG FLO
300 (1.524)
FPM (MPS)
1 (0.00508)
0
--
--
107
DO DIR.REV
0
--
1
0
--
--
{108}
RM RH
50
PCT
0.4
0
--
--
117
MINHOODVOLTS
1
VOLTS
0.01
0
--
--
{118}
RM CO2
1000
PPM
1
0
--
--
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.