Application

Point Database Application 2927
34
Siemens Industry, Inc.
Application Note, App 2927
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
96
CAL TIMER
12
HRS
1
0
--
--
97
SUPDUCT AREA
1.0
(0.09292)
SQ. FT (SQ
M)
0.025
(0.002323)
0
--
--
98
LOOP TIME
5
SEC
1
0
--
--
{99}
ERROR STATUS
0
--
1
0
--
--
104
SENSOR SEL
8
--
1
0
--
--
106
MODHTG FLO
300 (1.524)
FPM (MPS)
1 (0.00508)
0
--
--
107
DO DIR.REV
0
--
1
0
--
--
{108}
RM RH
50
PCT
0.4
0
--
--
117
MINHOODVOLTS
1
VOLTS
0.01
0
--
--
{118}
RM CO2
1000
PPM
1
0
--
--
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.