Application

Point Database (Slave Mode) Application 2997
36
Siemens Industry, Inc.
Application Note, App 2927
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
{84}
AI 5
74.0 (23.496)
DEG F
(DEG C)
0.5 (0.28)
37.5(3.056)
--
--
{94}
CAL AIR
NO
--
--
--
YES
NO
95
CAL SETUP
4
--
1
0
--
--
96
CAL TIMER
12
HRS
1
0
--
--
97
DUCT AREA 1
1.0 (0.09292)
SQ. FT (SQ
M)
0.025
(0.002323)
0
--
--
{99}
ERROR STATUS
0
--
1
0
--
--
104
SENSOR SEL
8
--
1
0
--
--
107
DO DIR.REV
0
--
1
0
--
--
{108}
RM RH
50
PCT
0.4
0
--
--
{118}
RM CO2
1000
PPM
1
0
--
--
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.