Commissioning Instructions

Before You Begin
Fume Hood Specific Sash Setup and Calibration
6 | 12
Siemens Industry, Inc.
Restricted
NOTE: If segment A and segment B dimensions are the same, only
setup segment A.
If all the sash panels in both segments are the same width, set PANL
WDTH 03 to this value.
If all even horizontal panels are one size and all odd horizontal panels
are another size.
a.
Set PANL WDTH 03 to the width of the odd sashes.
b.
Set PANL WDTH 04 to the width of the even sashes.
If all panels are different sizes.
a.
Set PANL WDTH 03 to the width of sash 3.
b.
Set PANL WDTH 04 to the width of sash 4.
c.
Set PANL WDTH 05 to the width of sash 5.
d.
Repeat until all sashes are defined.
8.
Measure the height of the top frame of sash 1 in inches (cm). The sash
frame holds the horizontal sash panels and occupies the outer edges of the
fume hood opening. Set TOP FRAME A to this measured value.
Top Frame Measurement with Air Foil Removed.
9.
Open sash 1 until the top edge of the vertical sash is aligned with the top
edge of the bypass area. Measure the height of the sash opening in inches
(cm). Set BYPASS HGHTA to this value.