Commissioning Instructions
Before You Begin
Fume Hood Specific Sash Setup and Calibration
8 | 12
Siemens Industry, Inc.
A6V10801619
Restricted
07.06.2016
Example Combination Sash Fume Hood with Fixed Area.
Sash Calibration
NOTE:
It is recommended that the vertical sash be calibrated before the horizontal
sashes.
Starting with the first side, side A.
1.
Set CAL SASH NUM to 1. It is recommended that the vertical sash be
calibrated before the horizontal sashes.
2.
Set CAL SASH LOC to MIN for minimum opening.
3.
Slide the vertical sash to the closed position. Set CAL SASH POS to 0
unless a physical stop prevents the sash from fully closing. If a physical stop
is present, measure the distance from the lower end of the vertical track to
the bottom of the sash in inches (cm). Set CAL SASH POS to this value.
When the sash aggregator accepts the reading, the minimum position value
will be automatically entered into POS SASH 1.
4.
Set CAL SASH LOC to MAX for maximum opening.
5.
Slide the vertical sash to the open position. Measure the distance from the
lower end of the track to the bottom edge of the sash panel in inches (cm).
Set CAL SASH POS to this value. When the sash aggregator accepts the
reading, the maximum position value will be automatically entered into POS
SASH 1 and CAL SASH POS will revert back to 257.