Desigo® Room Automation Room Condition Monitor (RCM II) RPM... The Siemens Room Condition Monitor provides flexible room environmental monitoring for Healthcare, Laboratories, Research Facilities and other pressurized spaces.
Features ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Flush mount to wall. Mounts in standard electrical boxes. High dust / moisture protection rating (IP55) for wash-down needs. No programing required. Four inputs and two outputs on-board. On-board or external main pressure transducer. High accuracy 0.25% sensor standard. 4…20 mA output pressure signal can be wired into room pressurization controller if necessary. Monitor pressure, temperature, humidity, air change rate and two user defined parameters.
Type summary Type Order number Description Pressure Range RPM.00-SD S55624-H130 Room Condition Monitor without sensor– Standard N/A RPM.12-SD S55624-H131 Room Condition Monitor with sensor 12/.05 ± 12 Pa (± 0.05 ”WC) RPM.25-SD S55624-H132 Room Condition Monitor with sensor 25/.1 ± 25 Pa (± 0.1 ”WC) RPM.62-SD S55624-H133 Room Condition Monitor with sensor 62/.25 ± 62 Pa (± 0.25 ”WC RPM.125-SD S55624-H134 Room Condition Monitor with sensor 125/.5 ± 12 Pa (± 0.05 ”WC) RPM.
Mounting Ensure rough-in box is ready to receive the Room Condition Monitor. a) Reference pressure side. b) 1-Gang electric box. c) Room pressure side. d) Room Condition Monitor (Display hinges down during installation then snaps in place when mounting is complete). e) Room Condition Monitor (may be mounted inside or outside room). f) Wall cavity. g) Electrical box (3-Gang double-deep if using on-board sensor, single deep if no on-board sensor).
Operation Device Configuration The Device Configuration menu is the series of menus that define all the operating parameters of the Room Condition Monitor. There are seven menu areas: ● Network – BACnet/IP or BACnet MS/TP network information is defined and tested. ● Inputs/Outputs – on-board or external hard-wired sensor points are defined. ● Room – room name, profiles and badges present are setup.
Technical data Housing Dimensions 215.0mm x 160.0mm x 16.51mm (9.25” W x 6.3” H x 0.65”D215) Weight 0.9 kg (2 lbs). Mounting Triple-gang, double deep electrical box. RACO 697, Appleton M3-350, or equivalent. Case Fire-retardant plastic UL94 V-0. Display 7” Projected Capacitive (PCAP) multitouch. 800 x 480 pixels. Usable with medical gloves. Display brightness 1…7 Audible alarm Dual piezo with 3 volume levels (0-75 dB max.) Pressure sensor specifications* Accuracy RSS ±0.
Inputs Digital Contact sensing voltage 3.3VDC Contact sensing current 1.5 Ma Contact resistance for closed contacts Max 50 ohms Contact resistance for open contacts Min 1K ohms Inputs pressure (internal) Type Range Pressure Pa, KPa, PSIi, cmWC, INWC, mmHG and cmHG -- Resolution Outputs Voltage measurement Analog Type Range Resolution Accuracy AI 0-10V 0-10V 2mV 10 mV / 0.1% FS AI 4-20mA 4-20mA .01mA (13 μA) 20 mA / 0.
Ambient conditions and protection classification Classification per IEC/EN 60730 Function of automatic control devices Pollution degree Overvoltage category Type 1 2 III Design type Device suited for use with equipment of safety classes I and II Degree of protection of housing to IEC EN 60529 Room automation station With terminal cover IP20 IP30 Degree of protection of housing to EN 60529 IP55 Chemical resistance Exposed surfaces are chemically resistant to vaporized hydrogen peroxide (VHP), formal
Connection Terminals Pin Description Ethernet RJ45 interface Terminal MS/TP BACnet MS/TP terminal Inputs (IN) 0-5 VDC, 0-10 VDC, or 4-20 mA input signal Configurable for either Analog or Digital signals. Use external sensors for pressure, temperature, humidity or any suitable application. Use as DI for door, HVAC filter DP, or duct static DP pressure switch. X1…X3, V+ *, ⏊ Analog Input (AI) Dedicated for use as input for either on-board pressure transducer, or general AI input.
Dimensions Issued by Siemens Industry, Inc. Smart Infrastructure 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 10 Siemens Industry, Inc. Smart Infrastructure Document ID A6V11402065_en Edition 2020-07-30 © Siemens Industry, Inc., 2020 Technical specifications and availability subject to change without notice.