Data Sheet for Product
2
Siemens Industry, Inc.
A6V11402065_en
Smart Infrastructure
2020-07-30
Features
● Flush mount to wall.
● Mounts in standard electrical boxes.
● High dust / moisture protection rating (IP55) for wash-down needs.
● No programing required.
● Four inputs and two outputs on-board.
● On-board or external main pressure transducer.
● High accuracy 0.25% sensor standard.
● 4…20 mA output pressure signal can be wired into room pressurization controller if
necessary.
● Monitor pressure, temperature, humidity, air change rate and two user defined parameters.
● Customizable room profiles.
● Two levels of password security.
● User-defined on-screen text and icons.
● Configuration options help reduce nuisance alarms.
● 50mm (2 in) wall depth when sensor is mounted remotely.
● Cloning features reduces time required for multi-unit installation.
Use
The Room Condition Monitor is designed for indoor use only to monitor critical environments by
providing differential pressure indication and additional parameters such as temperature, relative
humidity, air changes per hour, and user-defined information. Typically, this is between a
monitored room and a reference space such as a corridor or ante room. The unit also provides
monitoring, audio and visual alarming on all parameters and communications functions.
Typical Applications:
● Hospitals – patient isolation and protection rooms, operating suites, intensive care and
emergency rooms.
● Pharmaceutical, semiconductor, precision manufacturing and clean rooms
● Laboratories – medical research, BSL (bio safety labs), radiation, vivarium, toxic metals and
chemicals.
Functions
The Room Condition Monitor is designed to suit any pressurized room application, with the
ability to monitor up to 3 rooms. Software is preinstalled, with configuration and network
integration done using simple setup screens. There is no programming required. When
completed, configuration settings on one unit can be cloned to other devices using a standard
USB thumb drive, thereby shortening commissioning time. Units can also be configured remotely
over a BACnet network.
Mechanical design
A modular hardware design enables the Room Condition Monitor to fit in various wall
thicknesses found around the globe.
Mechanical design
The faceplate is attached to the unit body, enabling both tamper resistant operation and easy
opening for pressure calibration, if necessary.