Data Sheet for Product

7
Siemens Industry, Inc.
A6V11402065_en
Smart Infrastructure
2020-07-30
Inputs
Digital
Contact sensing voltage 3.3VDC
Contact sensing current 1.5 Ma
Contact resistance for closed contacts Max 50 ohms
Contact resistance for open contacts Min 1K ohms
Inputs
pressure (internal)
Type
Range
Resolution
Pressure Pa, KPa, PSIi, cmWC, INWC, mmHG and cmHG --
Outputs
Voltage measurement Analog
Type
Range
Resolution
Accuracy
AI 0-10V 0-10V 2mV 10 mV / 0.1% FS
AI 4-20mA 4-20mA .01mA (13 μA) 20 mA / 0.1% FS
Output
Relay
Contact resistance <50 mΩ at 10 mA/30 mV
Permissible load 60 W, 62.5 VA
DC 24V Supply for Field Devices
Output power 0.4 A Maximum
Protection against overload 200 mA, resetting
Interfaces
Ethernet/IP Plugs: 1 x RJ45, screened
Interface type: IPv4, Ethernet CAT5 cables
Protocol: BACnet over UDP/IP
MS/TP Interface type: RS485
Baud rates: 9600, 19200, 38400, 57600, 76800
3-conductor, twisted, shielded 16-24 AWG cable
Protocol: BACnet over MS/TP
USB Plug: Type B
Micro-USB port for configuration cloning between units and
software upgrades
Wiring connections
Pluggable screw terminals 2 or 3-conductor stranded unshielded twisted pair, 16-24
AWG (14-1.5 mm
2)
cross sectional area
Slotted screws Size 1, tightening torque 0.6 Nm (0.44 lb-ft).