Data Sheet for Product

9
Siemens Industry, Inc.
A6V11402065_en
Smart Infrastructure
2020-07-30
Pin
Description
Terminal
Ethernet RJ45 interface
MS/TP BACnet MS/TP terminal
+, -,
Inputs (IN) 0-5 VDC, 0-10 VDC, or 4-20 mA input signal
Configurable for either Analog or Digital signals.
Use external sensors for pressure, temperature, humidity or any
suitable application.
Use as DI for door, HVAC filter DP, or duct static DP pressure
switch.
X1…X3, V+ *,
Analog Input (AI) Dedicated for use as input for either on-board pressure transducer,
or general AI input. Used only when no transducer is purchased on
unit.
AI, V+,
Analog Output (OUT) 0-5 VDC, 0-10 VDC, or 4-20 mA output signal.
Used for pressure output signal or mirror an input signal. Can be
assigned to any room parameter.
VDC, mA,
Serial Proprietary
Not used at this time.
1…4
Relay 15 VDC SPDT NO/NC Relay. Use as remote alarm annunciator or
other NO/NC applications. Contact rating 2.0A @ 30 VDC /VA 0.6A
@125 VAC.
NO, C, NC, V+ *,
Power (24V~) 24 VAC (18-32 VAC operational), 50-60 HZ V~, V~
Earth ground
Wire Stranded shielded twisted pair, 16-24 AWG .14-1.5 mm2 cross
sectional area
* V+ is +24VDC, is signal ground.