Application

Point Databse Application 2920
43
Siemens Industry, Inc.
Application Note, App 2920
Point
Number
Descriptor
Factory
Default
(SI Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
{30}
GEX AIR VOL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
{31}
OCC SUP MAX
3400
(1604.46)
CFM
(LPS)
4 (1.8876)
0
--
--
{32}
OCC SUP MIN
340
(160.446)
CFM
(LPS)
4 (1.8876)
0
--
--
{33}
OCC GEX MAX
1100
(519.09)
CFM
(LPS)
4 (1.8876)
0
--
--
{34}
OCC GEX MIN
600 (283.14)
CFM
(LPS)
4 (1.8876)
0
--
--
{35}
SUP AIR VOL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
36
SUP FLO COEF
0.73
--
0.01
0
--
--
{37}
REHEAT AO1
0
VOLTS
0.01
0
--
--
38
DIF ALM DBD
100 (47.19)
CFM
(LPS)
4 (1.8876)
0
--
--
39
DIF ALM DEL
30
SEC
1
0
--
--
40
AVS FAILMODE
0
--
1
0
--
--
{41}
DO 1
OFF
--
--
--
ON
OFF
{42}
DO 2
OFF
--
--
--
ON
OFF
{43}
DO 3
OFF
--
--
--
ON
OFF
{44}
DO 4
OFF
--
--
--
ON
OFF
45
TRACK METHOD
FLOW
--
--
--
FLOW
STPT
{46}
DO 5
OFF
--
--
--
ON
OFF
{47}
ALARM DO7
OFF
--
--
--
ON
OFF
{48}
AUTOZERO DO8
OFF
--
--
--
ON
OFF
{49}
VALVE CMD
0
PCT
0.4
0
--
--
50
GEX VLV STAT
NOTCAL
--
--
--
NOTCAL
CAL OK
52
MAX HOOD VOL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
{53}
TOTL EXHAUST
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
54
GEX FLO COEF
0.73
--
0.01
0
--
--
{55}
SUP DMPR AO2
0
VOLTS
0.01
0
--
--
{56}
GEX DMPR AO3
0
VOLTS
0.01
0
--
--
57
VALVE CLOSED
10
VOLTS
0.01
0
--
--
58
VALVE OPEN
0
VOLTS
0.01
0
--
--
60
GEXDUCT AREA
1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0
--
--
{61}
OTHER SUP
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--