Application
Point Databse Application 2920
43
Siemens Industry, Inc.
Application Note, App 2920
140-1307
2015-07-07
Point
Number
Descriptor
Factory
Default
(SI Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
{30}
GEX AIR VOL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
{31}
OCC SUP MAX
3400
(1604.46)
CFM
(LPS)
4 (1.8876)
0
--
--
{32}
OCC SUP MIN
340
(160.446)
CFM
(LPS)
4 (1.8876)
0
--
--
{33}
OCC GEX MAX
1100
(519.09)
CFM
(LPS)
4 (1.8876)
0
--
--
{34}
OCC GEX MIN
600 (283.14)
CFM
(LPS)
4 (1.8876)
0
--
--
{35}
SUP AIR VOL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
36
SUP FLO COEF
0.73
--
0.01
0
--
--
{37}
REHEAT AO1
0
VOLTS
0.01
0
--
--
38
DIF ALM DBD
100 (47.19)
CFM
(LPS)
4 (1.8876)
0
--
--
39
DIF ALM DEL
30
SEC
1
0
--
--
40
AVS FAILMODE
0
--
1
0
--
--
{41}
DO 1
OFF
--
--
--
ON
OFF
{42}
DO 2
OFF
--
--
--
ON
OFF
{43}
DO 3
OFF
--
--
--
ON
OFF
{44}
DO 4
OFF
--
--
--
ON
OFF
45
TRACK METHOD
FLOW
--
--
--
FLOW
STPT
{46}
DO 5
OFF
--
--
--
ON
OFF
{47}
ALARM DO7
OFF
--
--
--
ON
OFF
{48}
AUTOZERO DO8
OFF
--
--
--
ON
OFF
{49}
VALVE CMD
0
PCT
0.4
0
--
--
50
GEX VLV STAT
NOTCAL
--
--
--
NOTCAL
CAL OK
52
MAX HOOD VOL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
{53}
TOTL EXHAUST
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
54
GEX FLO COEF
0.73
--
0.01
0
--
--
{55}
SUP DMPR AO2
0
VOLTS
0.01
0
--
--
{56}
GEX DMPR AO3
0
VOLTS
0.01
0
--
--
57
VALVE CLOSED
10
VOLTS
0.01
0
--
--
58
VALVE OPEN
0
VOLTS
0.01
0
--
--
60
GEXDUCT AREA
1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0
--
--
{61}
OTHER SUP
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--