Commissioning Instructions

Before You Begin
Fume Hood Specific Sash Setup and Calibration
5 | 11
Siemens Industry, Inc.
A6V10801622
Restricted
07.06.2016
Sash Setup 2958
1.
Set REPORT to OVERVIEW.
HZ PANEL CNT = 4
HZ PANEL CNT = 8
NOTE: Numbers on the sashes show how the sash is wired. After the
physical sashes are calibrated, the position of the sashes will display in POS
SASH 1, POS SASH 2, and so on.
2.
Determine the number of horizontal sash panels. This number includes the
horizontal sashes in both combination sashes. Set HZ PANEL CNT to this
value.
3.
Measure the width of the entire vertical fume hood face including the sash
frame in inches (cm). Set VSASH WIDTH to this value.
4.
Measure the length of the upper horizontal segment in inches (cm). Do not
include frame overlap in this measurement. Set TRACK WIDTHA to this
value.
5.
Measure the height of the upper individual horizontal sash panels in inches
(cm). Do not include any frame overlap in this measurement. All the sash
panels must be the same height. Set PANEL HGHTA to this value.
6.
Measure the length of the lower horizontal segment in inches (cm). Do not
include frame overlap in this measurement. Set TRACK WIDTHB to this
value.
7.
Measure the height of the lower individual horizontal sash panels in inches
(cm). Do not include any frame overlap in this measurement. All the sash
panels must be the same height. Set PANEL HGHTB to this value.
8.
Measure the width of the individual sash panels in inches (cm). Choose one
of the following:
If all the sash panels are the same width, set PANL WDTH 03 to this
value.
If all even horizontal panels are one size and all odd horizontal panels
are another size.
a.
Set PANL WDTH 03 to the width of the odd sashes.
b.
Set PANL WDTH 04 to the width of the even sashes.
If all panels are different sizes.