Operating Instructions

Product Overview
Siemens Building Technologies, Inc. 3
Hardware Inputs
Analog
Differential pressure transmitter
Digital
Operator Display Panel (ODP)
ATTN.UNATTN (through DI1)
OCC.UNOCC (through DI1)
Hardware Outputs
Analog
AO-E/AO-P module (Floating Control)
Operator Display Panel (ODP)
AO2 (Flow Signal, 1 to 10 Vdc)
Digital
FLN communications trunk
DO3 (24 Vac, Alarm/Hi.Low Output)
Power Wiring
The controller is powered by 24 Vac. Power wiring connects to the three screw terminals on
the controller labeled “C” (Common), “H” (Hot) and “E” (Ground) on the terminal block labeled
“TB1”. Earth ground connection is required (Figure 2).
Communication Wiring
The controller connects to the field panel by means of a Field Level Network (FLN) trunk.
Communication wiring connects to the three screw terminals on the controller labeled “+”
(positive), “-“ (negative), and “S” (Shield) (Figure 3).