Fume Hood Specific Sash Setup and Calibration
15
Siemens Industry, Inc. Start-up Procedures 140-1321
Restricted 2015-11-04
NOTE:
The fixed area of the fume hood is an area that remains open
regardless of sash position or movement. For example, most fume hoods
have an intake gap under the lower airfoil and above the cabinet of the fume
hood (typically a 1 inch gap). Also include 1% of the maximum open face area
in this calculation for other open areas, such as the space between the sash
and the track, and leakage.
Vertical Sash Fume Hood with Fixed Area.
8.
Set CAL SASH NUM to
1
.
9.
Set CAL SASH LOC to
MIN
for minimum opening.
10.
Close the sash door.
11.
Set CAL SASH POS to
0
inches (minimum) unless a physical stop prevents
the sash from fully closing. If a physical stop is present, measure the distance
from the lower end of the vertical track to the bottom of the sash in inches
(cm). Set CAL SASH POS to this value.
12.
Set CAL SASH LOC to
MAX
for maximum opening.
13.
Open the sash to the fully opened position.
14.
Measure the distance from the lower end of the vertical track to the bottom
edge of the sash in inches (cm). Set CAL SASH POS to this value
(maximum).
15.
Set CAL SASH NUM to
0
to turn the calibration sequence OFF.