Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Changing Exhaust Minimum
- Changing Exhaust Maximum
- Changing Face Velocity Setpoints and OCC Delay
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Remote Purge
- Fume Hood Specific Sash Setup and Calibration
- Setting External Face Area Input
- Setting Sash Area Alarms
- (Optional) Setting Damper Control — Application 2941
- Checkout of Damper — Application 2941
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting Airflow Control — Application 2942
- Range of Airflow Control — Application 2942
- Configuring Airflow Control — Application 2942
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Flashing Controller Firmware
Before You Begin
Configuring Airflow Control — Application 2942
29
Siemens Industry, Inc. Start-up Procedures 140-1321
Restricted 2015-11-04
PID Loop Only Operation (Mode 2)
NOTE:
The default P gain value is intended for PID operation in conjunction with the Venturi
table. When operating without the Venturi table the application is slower to respond.
Therefore, you should adjust the P gain as needed when operating in PID Only mode
to ensure acceptable performance.
The Venturi calibration table initially contains all zeros by default, that is, it contains no
calibration information. When the application detects a zero flow for the sixteenth entry
(the table entry with the highest flow), the application does operate, but runs with
only
PID control. If PID Only control is satisfactory for a given job, there is no need to
populate the Venturi tables.
Open Loop Operation (Mode 3)
To operate open loop control with manual entry of Venturi table:
1. Set OPEN LOOP to YES to indicate that the actuator is to operate open loop.
2. Use the
Venturi Table Evaluation and Editing
procedure. For additional information
on the open loop table values, see appropriate application manual.
To operate open loop control with automatic entry of Venturi table:
1. Temporarily connect an AVS flow sensor to the application.
2. Temporarily set OPEN LOOP to NO.
3. Initiate the Venturi calibration sequence as described earlier in this document
4. Remove the flow sensor.
5. Set OPEN LOOP to YES to indicate that the respective actuator is to operate open
loop.
Tuning the Flow Loops (Mode 1, 2)
NOTE:
This procedure does not apply to Venturi actuators that are configured to run open
loop.
CAUTION
Adjusting P gains (supply and/or exhaust) to values greater than 0.1 may cause
system instability.