Application

Sequence of Operation
Fail Mode Operation
40
Siemens Industry, Inc.
BACnet LCM-OAVS, Application 6760
Fail Mode Operation
If one of the controller’s accessories (inputs) fails, a failure mode sequence is initiated
that leads to the failure of VOL DIFFRNC. The following figure shows the order in
which points will fail.
* If MAX HOOD VOL is set to 0, a “Failed” status of HOOD VOL will not initiate a failure
in TOTL EXHAUST or VOL DIFFRNC. See
Fume Hood Flow Input
.
Air Velocity Sensors If one or both of the LCM air sensor signals (SUP AIR VOL,
GEX AIR VOL) are out of range (for example, improper wiring to/from the Offboard Air
Module(s), tubing not connected or connected backward), then the actions of the
supply and general exhaust Venturi Air Valves will depend on the value of AVS
FAILMODE. Once GEX AIR VOL and SUP AIR VOL are normal, the supply and
general exhaust Venturi Air Valves return to normal operation.
See
Operation of AVS FAILMODE
for more information.
Fume Hood Flow If MINHOODVOLTS is 1 Volt or higher, HOOD VOL will fail when
the LCM receives an invalid (less than .4 Vdc) fume hood flow signal or when the fume
hood controller (FHC) loses power or when it loses its flow sensor. If HOOD VOL fails
and if VOL DIF STPT is greater than or equal to 0 (negative or neutral pressurization
required), the supply and exhaust loops assume a hood exhaust value of 0 cfm and
continue to maintain user-defined pressurization. If HOOD VOL fails and VOL DIF
STPT is less than 0 (positive pressurization required), the supply and exhaust loops
assume the hood's exhaust value is equal to MAX HOOD VOL and continue to
maintain user-defined pressurization. When the LCM is being used with fume hoods,
and MAX HOOD VOL is set above its default of 0 cfm, a failure of HOOD VOL causes
TOTL EXHAUST and VOL DIFFRNC to fail in succession. When VOL DIFFRNC fails,
the pressurization alarm point, VOL DIF ALM, turns on automatically. If any of these
points have been defined as alarmable and unbundled at the field panel, an alarm will
be annunciated across the network.
If MINHOODVOLTS is set to a value less than 1 (including 0), the fail voltage sensing
at .4 Vdc as described above is disabled. However, if there is a break (open circuit) in
the wiring, both the AI 3 point and HOOD VOL point will indicate failure.