Commissioning Instructions

Before You Begin
Fume Hood Specific Sash Setup and Calibration
7 | 10
Siemens Industry, Inc.
A6V10801608
Restricted
07.06.2016
Sash Calibration
NOTE:
The full travel of the sash must be used during calibration.
1.
Set CAL SASH NUM to 1.
2.
Verify CAL SASH LOC is set to MIN.
3.
Slide vertical sash 1 to the closed position. Measure the distance from the
bottom of vertical sash 1 to the bottom of the sash opening in inches (cm).
Set CAL SASH POS to this value. When the SOAM accepts the reading,
CAL SASH POS will revert back to
257 and CAL SASH LOC will switch to
MAX.
4.
Verify CAL SASH LOC is set to MAX.
5.
Slide vertical sash 1 to the full open position. Measure the distance from the
bottom of vertical sash 1 to the bottom of the sash opening in inches (cm).
Set CAL SASH POS to this value. When the SOAM accepts the reading, the
maximum position value will be automatically entered into POS SASH 1 and
CAL SASH POS will revert back to
257, CAL SASH LOC will switch to MIN,
and CAL SASH NUM will return to
0.
6.
Set CAL SASH NUM to 2.
7.
Verify CAL SASH LOC is set to MIN.
8.
Slide vertical sash 2 to the closed position. Measure the distance from the
bottom of vertical sash 2 to the bottom of the sash opening in inches (cm).
Set CAL SASH POS to this value. When the SOAM accepts the reading,
CAL SASH POS will revert back to 257 and CAL SASH LOC will switch to
MAX.
9.
Verify CAL SASH LOC is set to MAX.
10.
Slide vertical sash 2 to the full open position. Measure the distance from the
bottom of vertical sash 2 to the bottom of the sash opening in inches (cm).
Set CAL SASH POS to this value. When the SOAM accepts the reading, the
maximum position value will be automatically entered into POS SASH 2 and
CAL SASH POS will revert back to
257, CAL SASH LOC will switch to MIN,
and CAL SASH NUM will return to
0.
11.
If SEG COUNT = 2, repeat Steps 1 through 10 for segment B sash panels.