Data Sheet for Product
Technical Specification Sheet
Document No. 149-319P25
Mar 12, 2019
Siemens Industry, Inc. Page 1 of 19
Laboratory Room Single Duct Supply Air
Terminal
Figure 1. Laboratory Room Single Duct Supply
Air Terminal.
The Laboratory Room Single Duct Supply Air
Terminal is an industrial-grade, easy-to-install pre-
packaged airflow measurement and control terminal
unit. The Laboratory Room Single Duct Supply Air
Terminal is a round inlet, rectangular outlet, one piece
insulated and lined terminal that provides cooling only
or cooling with hot water reheat. When used with the
Laboratory Room Controller, it provides fast acting,
stable and precise laboratory supply airflow control
over the entire range of room airflow requirements.
Measurement of airflow is accomplished by four
quadrant sensing technology to achieve
measurement accuracy of 3% of actual flow (sensor
only) when tested in accordance with AMCA 610.
Airflow control is achieved utilizing a round single
blade damper mounted on a zinc plated steel shaft
with polyethylene bushings and mechanical stops.
Construction is 22 gauge-galvanized steel, including
the casing and damper.
Features
· Eight standard sizes with airflow capacities from
35 to 8530 cfm; others are also available.
· Four quadrant airflow sensors with multi-point,
center averaging and signal amplification.
· Low radiated and discharge sound levels.
· 22 gauge casing with slip and drive discharge
connection.
· Solid zinc plated steel damper shaft on self
lubricating polyethylene bushings for fast acting
control and maintenance free operation.
· Low non-recoverable static pressure loss.
· Round, beaded inlet collar accepts nominal
flexible or rigid duct (size 18 has rectangular
inlet).
· Internal insulation 3/4-inch fiber-free foam which
meets requirements of NFPA 90A and UL181.
Closed cell structure foam allows for disinfecting
and hand washing with detergents and water.
· Meets mechanical standards UL 181, NFPA 90A,
ASTM E84, UL 723 and bacteria standard ASTM
C665.
· Ultra-low leakage, damper and casing (standard
without reheat). ULL with reheat available as
custom option.
· Up to four rows of hot water reheat coils.
· Meets equipment requirements of ASHRAE 62.1
Sec. 5.
· Clean, sealed shipping bags available for LEED
IEQ projects.
· Lab DXR (IP) control packages available