Description
The Single Duct Supply Terminal consists of the
following components (see Figures 2 through 6).
· Galvanized steel round inlet duct, damper blade
in sizes from 4” (10.2 cm) to 16” (40.6 cm)
diameter; size 18 unit has a rectangular 16 × 24
inlet and two 16” (40.6 cm) diameter dampers.
· Four quadrant airflow measurement sensor.
· Rectangular, lined and insulated casing with slip
and drive outlet connections.
· Factory-mounted controls options.
· Electronic damper control – high speed or
standard speed
Specifications
Materials (within air stream) – Standard
Duct Casing
22 gauge galvanized steel with
mechanically locked and sealed
seam
Airflow Sensor
PVC sensing arms and
center manifold with galvanized
steel frame
Damper Blade
22 gauge, galvanized steel single
damper with Volara foam gasket
Damper Shaft
1/2-inch (1.27 cm) diameter, zinc-
plated steel. Shaft end marked
with the damper blade position
Damper Bushing Self lubricating polyethylene
Case Insulation
3/4-fiber free foam. Density
1.5 lb/ft3
Meets NFPA 90A UL181
Flame Spread rating <25
Smoke Developed rating < 50
Meets ASTM E84 UL 723,
bacteria stand. ASTM C665
Hot water reheat coils
(optional)
22 gauge, galvanized casing,
Aluminum sine wave fins
(thickness 0.0045”)
Copper tubes, 0.016”wall
Meets ARI 410
Dimensions
Sizes See Figures 4, 5, 6 and 7
Weight 19 to 63 lbs. (8.6 to 28.6 kg)
Materials (outside air stream) - Standard
Control Enclosure
18 gauge two piece galvanized
steel
Pneumatic Tubing
UL rated 94 V-2 fire retardant
polyethylene
Pneumatic Fittings Brass, dual barbed
Airflow Measurement
Sensor Type
Four quadrant, with 12 sensing
points, center averaging, and
signal amplification
Accuracy
Flow Measurement
±3% of actual flow @ listed ranges
(Sensor only, per AMCA 610)
Installation
Requirements
Rigid duct of the same diameter
1 × duct diameters upstream from
the sensor, or taper angle less
than 30 degrees
Airflow Control
Damper Blade
Round, sealing single blade with
90 degree control with two
mechanical stops
Non-Recoverable Terminal
Pressure Loss See Table 2
Environmental
Operating
Temperature/% rh
40 to 120°F (4 to 50°C)
0 to 95% non-condensing
Storage
Temperature/% rh
-10 to 150°F (-23 to 65°C)
0 to 95% non-condensing
Figure 2. Single Duct Supply Air Terminal Components