Operating Instructions

Chapter 3 Point Database
13
Siemens Industry, Inc.
Owner's Manual
Descriptor
Address
1
Application
Description
HTG FLO MIN
33
2963
The minimum amount of air in cfm (lps) to be supplied to the
space in heating mode.
HTG FLO MAX
34
2963
The maximum amount of air in cfm (lps) to be supplied to the
space in heating mode.
SUP FLO
{35}
2963
Actual amount of air in cfm (lps) currently passing through the
air velocity sensor.
SUP FLO COEF
36
2963
Calibration factor for airflow.
REHEAT CMD
{37}
2963, 2965
The value to which the reheat modulation is commanded.
RAD VALV CMD
{38}
2963, 2965
Used to set the value of the radiation valve.
DIS TEMP MAX
{39}
2963, 2965
The maximum value to which DISCH STPT can be set by the
room control loop.
AVS FAIL MODE
40
2963, 2965
Indicates the desired position of the dampers if the airflow
sensor(s) fail.
Valid input: CLOSED or OPEN.
DO 1
{41}
2963, 2965
Digital output 1 controls a 24 Vac load with an ON or OFF
status. If Motor 1 is enabled, then DO 1 is coupled with DO 2 to
control an actuator.
DO 2
{42}
2963, 2965
Digital output 2 controls a 24 Vac load with an ON or OFF
status. If Motor 1 is enabled, then DO 2 is coupled with DO 1 to
control an actuator.
DO 3
{43}
2963, 2965
Digital output 3 controls a 24 Vac load with an ON or OFF
status. If Motor 2 is enabled, then DO 3 is coupled with DO 4 to
control an actuator.
DO 4
{44}
2
2963, 2965
Digital output 4 controls a 24 Vac load with an ON or OFF
status. If Motor 2 is enabled, then DO 4 is coupled with DO 3 to
control an actuator.
DO 5
{45}
2963, 2965
Digital output 5 controls a 24 Vac load with an ON or OFF
status. If Motor 3 is used, this point is coupled with DO 6.
DO 6
{46}
2963, 2965
Digital output 6 controls a 24 Vac load with an ON or OFF
status. If Motor 3 is used, this point is coupled with DO 5.
ALARM DO 7
{47}
2963, 2965
The value to which the cold duct damper motor is commanded
in percent of full travel.
SUP DMP CMD
{48}
2963, 2965
The value to which the supply damper motor is commanded in
percent of full travel.
SUP DMP POS
{49}
2963, 2965
The current position of the supply damper motor in percent of
full travel. This value is calculated based on motor run time.
REHEAT START
50
2963
Determines how the reheat modulation will be sequenced while
in heating mode. When HTG LOOPOUT is above this value,
then the reheat modulates upward.
PRESS STATE
{51}
2963
A software command that can override the physical position of
the switch on DI 6.
GEX DMP CMD
{52}
2963, 2965
The value to which the general exhaust damper motor is
commanded in percent of full travel.
GEX DMP POS
{53}
2963, 2965
The current position of the general exhaust damper motor in
percent of full travel. This value is calculated based on motor
run time.