Chapter 3 Point Database
15
Siemens Industry, Inc.
Owner's Manual
Descriptor
Address
1
Application
Description
AOV1
{74}
2963, 2965
Displays the voltage signal to AO1.
AOV2
{75}
2
2963, 2965
Displays the voltage signal to AO2.
TEMP CTL VOL
{76}
2963
The temperature control loop volume.
RAD START
77
2963
The value of heating command at which the radiation valve is
fully closed.
CTL TEMP
{78}
2963, 2965
The temperature used as input for the temperature control
loops. This value will be the same as the value in ROOM
TEMP, unless it is overridden.
CLG LOOPOUT
{79}
2963
The cooling temperature control loop output value in percent.
HTG LOOPOUT
80
2963
The heating temperature control loop output value in percent.
TOTL EXHAUST
{81}
2963, 2965
This value is the sum of the measured value of the airflow from
the room through the general exhaust terminal, the airflow
through the fume hoods, and any exhaust flows not connected
to the PRC.
TRACK METHOD
82
2963
Determines whether the controller uses FLOW or STPT flow
tracking. When the value is STPT, the supply flow follows the
GEN EXH STPT. When the value is FLOW, the supply flow
follows GEN EXH VOL.
RAD END
83
2963, 2965
The value of heating command at which the radiation valve is
fully open.
GEX STPT
{85}
2963
The general exhaust setpoint.
GEX MIN
86
2963
The minimum general exhaust in unoccupied mode.
GEX MAX
87
2963
The maximum general exhaust in unoccupied mode.
VOL DIF STPT
{88}
2963
The desired value for the flow difference. This value can be
selected and adjusted to achieve room pressurization.
OTHER EXH
{89}
2963
The value of any exhaust airflows not connected to the LCM.
Must be entered to the controller to account for flows it cannot
detect.
SWITCH DBAND
90
2963
The temperature range in degrees which is compared to the
difference between CTL TEMP and CTL STPT. The difference
must exceed this value for temperature control mode to change
over. Changeover is also subject to the active temperature
control loop output being below SWITCH LIMIT and SWITCH
TIME being expired.
HC.ENDIS
91
2963
The setup point to either enable or disable heating and/or
cooling modes.
CTL STPT
{92}
2963
The actual setpoint value being used as input for the active
temperature control loop.
SUP STPT
{93}
2963
The setpoint of the supply flow control loop.
CAL AIR
{94}
2963, 2965
YES commands the controller to go through calibration
sequence for the air velocity transducers. YES is also displayed
when the calibration sequence is started automatically. CAL
AIR automatically returns to NO after the calibration sequence
is completed. Valid input: YES or NO.
CAL SETUP
95
2963, 2965
The configuration setup code for the calibration sequence
options.