Operating Instructions

Chapter 3 Point Database
17
Siemens Industry, Inc.
Owner's Manual
Descriptor
Address
1
Application
Description
FAIL TIME
121
2963
Indicates when the air volume is too far away from setpoint for
too long.
ALARM ENA
122
2963
An analog point that determines if and what alarm activates
ALARM DO7.
MTR SETUP
123
2963, 2965
Sets the presence or absence of a motor and its direction of
travel.
DO DIR.REV
124
2963, 2965
Reverses the output state for selected non-motor digital
outputs.
VENT ALM DEL
125
2963
Delay period that prevents “nuisance alarms” on the air change
rate.
DIF ALM DBD
126
2963
Setting for the controller’s alarm; should be set lower than VOL
DIF STPT to avoid losing pressurization completely.
DISCH I GAIN
127
2963
Integral feedback gain used to tune the discharge temperature
control.
1)
Points not listed are not used in this application.
2)
Point numbers that appear in brackets { } may be unbundled at the field panel.