Application

Sequence of Operation
AVS Calibration
16
Siemens Industry, Inc.
Application Note, App 2926
AVS Calibration
Calibration of the air velocity transducer(s) is periodically required to maintain accurate
air velocity readings. Depending on the value of CAL SETUP, calibration takes place
either at fixed time intervals or whenever the application goes into unoccupied mode.
When calibration is in progress, CAL AIR equals YES. After calibration, CAL AIR
returns to NO.
The application uses Autozero Modules connected to AUTOZERO DO8. This means
that the supply and general exhaust flow control devices do not close during calibration
of the transducers.
NOTE:
The LCM does not monitor Fume Hood flow changes for 3 seconds during AVS
calibration.
Venturi Air Valve Calibration (Mode 1, 3)
Calibration of the Venturi Air Valve(s) must be performed at least once during start-up
to determine the relationship between airflow and the voltage curve of the actuator.
WARNING
The LCM cannot calibrate the supply and general exhaust Venturi Valves at the same
time.
They must be calibrated separately.
Prerequisites for calibrating Venturi Air Valves:
Fully operational supply and general exhaust airflow systems.
Supply and general exhaust Air Velocity Sensors are calibrated and working
normally (SUP AIR VOL and GEX AIR VOL cannot be Failed).
The supply or general exhaust Venturi Air Valve is calibrated by setting CAL SUP VLV
or CAL GEX VLV to YES. Calibration proceeds automatically and takes about 3
minutes, after which CAL SUP VLV (or CAL GEX VLV) returns to NO. If calibration is
successful, SUP VLV STAT, or GEX VLV STAT, is set to PASS. A failed calibration
requires checking the equipment for possible causesloose or kinked flow sensor
tubes, improper actuator or valve operation, etc.followed by recalibration.
NOTE:
The factory default value of SUP VLV STAT and GEX VLV STAT is NOTCAL. The
value of SUP VLV STAT or GEX VLV STAT is set whenever a calibration or table
transfer is performed as the last step of the calibration/table transfer. SUP VLV STAT
and GEX VLV STAT are never used for active control decisions.
When calibration is complete, the EEPROM automatically stores a table statement of
voltages (no loss of values upon power failure) that will be output to the AO point, SUP
DMPR AO2 or GEX DMPR AO3, to drive the actuator.