Application

Sequence of Operation
Operation of AVS FAILMODE
37
Siemens Industry, Inc.
Application Note, App 2926
Operation of AVS FAILMODE
AVS FAILMODE is an enumerated point that describes how the supply Venturi Air
Valve and the general exhaust Venturi Air Valve will respond if one or both Air Velocity
Sensors (AVS) fail. It can handle both positively pressurized rooms and negatively
pressurized rooms.
The default value of AVS FAILMODE is
0. This default causes both the supply and
general exhaust to hold their current position when an AVS fails. Open Supply, Open
Exhaust and Close Supply, Close Exhaust are not defined AVS FAILMODE states.
AVS Failure and AVS FAILMODE Table Values.
AVS FAILMODE
0
(default)
Hold Supply, Hold General Exhaust
1
Hold Supply, Open General Exhaust
2
Hold Supply, Close General Exhaust
3
Open Supply, Hold General Exhaust
4
Close Supply, Hold General Exhaust
5
Close Supply, Open General Exhaust
6
Open Supply, Close General Exhaust
7
VENTILATION
8
PRESSURE
AVS FAILMODE values are not additive. For example, if AVS FAILMODE equals
3,
this means to open the supply Venturi Air Valve and hold the general exhaust Venturi
Air Valve if an AVS fails.
The first seven values of AVS FAILMODE (0 through 6) describe specific actions taken
when an AVS fails. For example, if AVS FAILMODE equals
5, then whenever an AVS
fails, the supply Venturi Air Valve will always close and the general exhaust Venturi Air
Valve will always open.
The last two values of AVS FAILMODE do not describe specific actions; that is, when
an AVS fails, the supply and general exhaust will react differently depending on the
circumstances.
If AVS FAILMODE equals
7, the supply Venturi Air Valve will hold. The general
exhaust Venturi Air Valve will also hold if a fume hood is present (that is, if MAX HOOD
VOL > 0). If a fume hood is absent, then the general exhaust Venturi Air Valve will
close if the room is being positively pressurized and open if the room is neutral or
negatively pressurized (that is if VOL DIF STPT is equal to or greater than 0).
If AVS FAILMODE equals
8, the supply Venturi Air Valve will open if the room is being
positively pressurized and close if the room is neutral or negatively pressurized. The
general exhaust Venturi Air Valvewill hold if a fume hood is present. If a fume hood is
absent, the general exhaust Venturi Air Valve will close if the room is being positively
pressurized and open if the room is neutral or negatively pressurized.
NOTE:
If AVS FAILMODE is set greater than 8, it will default to 0.