Application

Point Database Application 2926
46
Siemens Industry, Inc.
Application Note, App 2926
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
63
ROOM P GAIN
2
--
0.05
0
--
--
64
ROOM I GAIN
0.001
--
0.0001
0
--
--
{67}
UOC GEX MAX
1000
(471.9)
CFM (LPS)
4 (1.8876)
0
--
--
{68}
UOC GEX MIN
500
(235.95)
CFM (LPS)
4 (1.8876)
0
--
--
{69}
TOTL SUPPLY
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
70
SUP P GAIN
0.015
--
0.001
0
--
--
{71}
UOC SUP MAX
2200
(1038.18)
CFM (LPS)
4 (1.8876)
0
--
--
{72}
UOC SUP MIN
220
(103.818)
CFM (LPS)
4 (1.8876)
0
--
--
{73}
CTL STPT
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{74}
HOOD VOL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{75}
DISCH STPT
60.0
(15.656)
DEG F
(DEG C)
0.5 (0.28)
37.5(3.056)
--
--
76
VOLUME STATE
1
--
1
0
--
--
{77}
DO 6
OFF
--
--
--
ON
OFF
{78}
CTL TEMP
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{79}
TEMP LOOPOUT
0.0 (0.0)
DEG F
(DEG C)
0.1 (0.0556)
-100.0 (-55.6)
--
--
80
DISCH P GAIN
2.0 (3.6)
--
0.05 (0.09)
0
--
--
81
DISCH I GAIN
0.02 (0.036)
--
0.0002
(0.00036)
0
--
--
{83}
VOL DIFFRNC
0 (-0.0001)
CFM (LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
{84}
DISCH TEMP
74.0
(23.496)
DEG F
(DEG C)
0.5 (0.28)
37.5(3.056)
--
--
{85}
GEX FLO STPT
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
86
FAIL LIMIT
40 (18.876)
CFM (LPS)
4 (1.8876)
0
--
--
{87}
CAL GEX VLV
NO
--
--
--
YES
NO
{88}
VOL DIF STPT
400
(188.7599)
CFM (LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
{89}
OTHER EXH
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
90
OC V ALM LVL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
91
UC V ALM LVL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{92}
VENT ALM
OFF
--
--
--
ON
OFF
{93}
SUP FLO STPT
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{94}
CAL AIR
NO
--
--
--
YES
NO
95
CAL SETUP
4
--
1
0
--
--