Application
Point Database Application 2926
46
Siemens Industry, Inc.
Application Note, App 2926
140-1308
2015-07-07
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
63
ROOM P GAIN
2
--
0.05
0
--
--
64
ROOM I GAIN
0.001
--
0.0001
0
--
--
{67}
UOC GEX MAX
1000
(471.9)
CFM (LPS)
4 (1.8876)
0
--
--
{68}
UOC GEX MIN
500
(235.95)
CFM (LPS)
4 (1.8876)
0
--
--
{69}
TOTL SUPPLY
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
70
SUP P GAIN
0.015
--
0.001
0
--
--
{71}
UOC SUP MAX
2200
(1038.18)
CFM (LPS)
4 (1.8876)
0
--
--
{72}
UOC SUP MIN
220
(103.818)
CFM (LPS)
4 (1.8876)
0
--
--
{73}
CTL STPT
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{74}
HOOD VOL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{75}
DISCH STPT
60.0
(15.656)
DEG F
(DEG C)
0.5 (0.28)
37.5(3.056)
--
--
76
VOLUME STATE
1
--
1
0
--
--
{77}
DO 6
OFF
--
--
--
ON
OFF
{78}
CTL TEMP
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{79}
TEMP LOOPOUT
0.0 (0.0)
DEG F
(DEG C)
0.1 (0.0556)
-100.0 (-55.6)
--
--
80
DISCH P GAIN
2.0 (3.6)
--
0.05 (0.09)
0
--
--
81
DISCH I GAIN
0.02 (0.036)
--
0.0002
(0.00036)
0
--
--
{83}
VOL DIFFRNC
0 (-0.0001)
CFM (LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
{84}
DISCH TEMP
74.0
(23.496)
DEG F
(DEG C)
0.5 (0.28)
37.5(3.056)
--
--
{85}
GEX FLO STPT
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
86
FAIL LIMIT
40 (18.876)
CFM (LPS)
4 (1.8876)
0
--
--
{87}
CAL GEX VLV
NO
--
--
--
YES
NO
{88}
VOL DIF STPT
400
(188.7599)
CFM (LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
{89}
OTHER EXH
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
90
OC V ALM LVL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
91
UC V ALM LVL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{92}
VENT ALM
OFF
--
--
--
ON
OFF
{93}
SUP FLO STPT
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{94}
CAL AIR
NO
--
--
--
YES
NO
95
CAL SETUP
4
--
1
0
--
--