Application

Point Database Application 2926
47
Siemens Industry, Inc.
Application Note, App 2926
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
96
CAL TIMER
12
HRS
1
0
--
--
97
SUPDUCT AREA
1.0
(0.09292)
SQ. FT (SQ
M)
0.025
(0.002323)
0
--
--
98
LOOP TIME
5
SEC
1
0
--
--
{99}
ERROR STATUS
0
--
1
0
--
--
104
SENSOR SEL
8
--
1
0
--
--
105
VENTURI ACT
1
--
1
0
--
--
106
MODHTG FLO
300 (1.524)
FPM (MPS)
1 (0.00508)
0
--
--
107
DO DIR.REV
0
--
1
0
--
--
{108}
RM RH
50
PCT
0.4
0
--
--
109
FAIL TIME
60
SEC
2
0
--
--
117
MINHOODVOLTS
1
VOLTS
0.01
0
--
--
{118}
RM CO2
1000
PPM
1
0
--
--
{119}
TABLE VOLTS
0
VOLTS
0.01
0
--
--
{120}
V TABLE PT
0
--
1
0
--
--
121
HI LIMIT
1
--
0.01
0
--
--
122
LO LIMIT
1
--
0.01
0
--
--
123
S OPEN LOOP
NO
--
--
--
YES
NO
124
G OPEN LOOP
NO
--
--
--
YES
NO
125
SUP MAX RATE
0 (0.0)
FPM (MPS)
1 (0.00508)
0
--
--
126
GEX MAX RATE
0 (0.0)
FPM (MPS)
1 (0.00508)
0
--
--
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.