Chapter 10–Laboratory Ventilation System - Validation
PRIMARY AIR HANDLING UNIT 5W
OUTSIDE AIR
TEMP. 65.3 F
RH 62%
HWS
HWR
HTG DISCH.
AIR 65.8 F
STATIC
PRESSURE
1.85" W.C.
SUPPLY AIR
TO 5TH FLR
WEST ZONE
HUMIDIFIER
STEAM 10.2 PSI
SUPPLY AIR
54.4 F
CHWS
CHWR
C
COOLING COIL
VALVE OPEN
37%
HEATING COIL
VALVE OPEN
20%
OUTSI DE
AIR
FILTER
NORMAL
SUPPLY
FAN ON
NORMAL
H
CLG DISCH.
AIR 54.8 F
Figure 23. Laboratory Air Handling Unit Showing Current Operating Parameters.
92 Siemens Building Technologies, Inc.
FUME HOOD C24
FACE VEL 106 FPM (NORMAL)
SASH OPEN 15 "
FUME HOOD C25
FACE VEL 96 FPM (NORMAL)
SASH OPEN 8 "
BIOSAFETY CAB. M13
EXH FAN OFF (NORMAL)
FILTER (NORMAL)
LABORATORY CB 12
ROOM TEMP
73.2 F (NORMAL)
ROOM RH
32 % (LOW)
FIRE ALARM (NORMAL)
CHEM EMG. (NORMAL)
MED EMG. (NORMAL)
ROOM PRESS
- 0.02 " (NORMAL)
BIOSAFETY CAB. M12
EXH FAN ON (NORMAL)
FILTER (NORMAL)
Figure 24. Laboratory Room Showing Current Values of Monitored Points.