Basic Documentation
Table Of Contents
Technology Report
February, 2003
Siemens Industry, Inc. Page 1 of 8
Fume Hood Face Velocity Control
Sash Position Sensing vs. Side Wall Sensing
A question is often raised regarding the preferred
method of controlling fume hood face velocity
particularly with variable air volume (VAV) fume
hoods. Just to recap, the objective of VAV fume
hood face velocity control is to:
maintain the fume hood's average face velocity
at a constant value regardless of the size of the
fume hood's sash opening.
minimize energy usage and enhance fume hood
containment.
Methods of Face Velocity Control
The two predominant methods for controlling fume
hood face velocity are sash position sensing and
side wall sensing. In sash position sensing the
controller determines the size of the sash opening
by one or more sash position sensors. The controller
then adjusts the fume hood's exhaust airflow in
relation to the size of the sash opening. This results
in a specific amount of makeup air being drawn
through the sash opening, which can be expressed
as the fume hood's average face velocity.
For instance, if an average face velocity of 100 feet
per minute (fpm) is desired and the fume hood's
open area is determined to be 4 square feet, a fume
hood exhaust of 400 cubic feet per minute (cfm) will
be maintained. This will cause 400 cfm of makeup
air to be drawn through the 4 square foot open area
resulting in an average air (face) velocity of 100 fpm.
Similarly, if the total open area were 6 square feet,
the fume hood exhaust would be increased to 600
cfm to maintain the same 100 fpm average face
velocity.
With side wall sensing, the controller senses the
velocity of the makeup air being drawn through the
open sash area and adjusts the fume hood's
exhaust as needed to maintain the makeup airflow
at the required air (face) velocity. The airflow velocity
sensor is normally located in the fume hood's side
wall so it won't interfere with fume hood usage.
Thus, this type of face velocity control is normally
referred to as side wall sensing.
Figure 1 illustrates these two different control
approaches.
Figure 1
. Sash Position Sensing and Side Wall Sensing for a Single Vertical Sash Fume Hood.
Document No. 1
49-975