Commissioning Instructions

Before You Begin
Setting Blank Display
10
Siemens Industry, Inc. 140-1318
Restricted 2015-11-04
NOTE:
The air velocity sensor should be calibrated at least once every 24 hours. Make sure
that the sensor has been calibrated before balancing takes place, as this will affect
the balancer’s results.
CAL SETUP Options.
CAL SETUP
Option Values
Description
0 Calibration occurs ONLY when CAL AIR is set to YES.
1 Calibration occurs with an occupied to unoccupied mode changeover.
4
(factory default
mode)
Calibration occurs on the time interval set in CAL TIMER.
Example:
If CAL TIMER = 12, then the calibration period is 12 hours. In this
option, actual calibration is subject to a time delay of up to 10 minutes to
prevent it from interfering with a response to fume hood flow change(s).
This is the recommended option when using a controller with an Autozero
Module.
Setting Blank Display
Set BLANK DSPLY to NO in order to display airflow readings at the ODP.
NOTE:
If BLANK DSPLY is set to YES, alarms will still display at the ODP.
Setting Display Weight
Set DISPLAY WT to a value of 0 through 100% (default is 100%). The suggested value
is 30%.
NOTE:
If DISPLAY WT is set to 100%, the exhaust volume displayed at the ODP may
fluctuate rapidly. This rapid fluctuation is due to the constant adjustments of the FHC.
When DISPLAY WT is set to a value less than 100%, the exhaust volume displayed
at the ODP is a weighted calculated value. This value is used to stabilize the ODP
displayed value only; it has no effect on the control sequence.
If you set DISPLAY WT to zero, the Operator Display Panel will “freeze” at the last
read value. Setting DISPLAY WT to a value other than zero (suggested value is 30%)
allows the Operator Display Panel to update the displayed exhaust volume.
Setting Display Resolution
Set DISPLAY RES to a value of 0 through 255 cfm (0 to 120 lps). The default is 20 cfm
(9.4 lps). This value is used as a COV limit for face velocity readings displayed at the
ODP only; it has no affect on the control sequence and has no effect on values going
across the network.