Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Setting High Flow Setpoint
- Setting Low Flow Setpoint
- Setting ODP Display
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Damper Control
- Checkout of Damper
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Flashing Controller Firmware
Before You Begin
Setting High Flow Setpoint
11
Siemens Industry, Inc. 140-1318
Restricted 2015-11-04
NOTE:
If you set DISPLAY RES to zero, the Operator Display Panel will “freeze” at the
exhaust volume setpoint EXH VOL STPT. Setting DISPLAY RES to a value other
than zero allows the Operator Display Panel to update the displayed exhaust volume.
Setting High Flow Setpoint
Set EXH HI STPT to the desired air volume. Values are in CFM (LPS). The valid range
of values will depend on the size of the exhaust duct.
Setting Low Flow Setpoint
Set EXH LO STPT to the desired air volume. Values are in CFM (LPS). The valid
range of values will depend on the size of the exhaust duct.
Setting ODP Display
Set ODP DISPLAY to the desired value. Values are CFM or MODE. In CFM, the ODP
displays the exhausted CFM. Use the table below to set the value. The default value is
MODE.
ODP
Display
Flow
Setpoint
Actual display
on the ODP
Cfm HI Cfm
Low Cfm
Mode HI
Low
Setting Hi and Low Warn Limits
Skip this step unless there is a special requirement on the job; the default will be used.
1.
Change report to
STARTUP
.
2.
Set HI WARN LMT and LOW WARN LMT.
These limits are defined as a percentage of the controlled setpoint, meaning
that the alarm limits will be closer as the EXH STPT decreases. The default
values are 135% and 85% respectively. These points may be adjusted to
meet customer requirements.