Commissioning Instructions

Before You Begin
Flashing Controller Firmware
19
Siemens Industry, Inc. 140-1318
Restricted 2015-11-04
Flashing Controller Firmware
NOTE:
When re-loading/flashing firmware, existing PPCL may no longer function correctly.
FLT Procedure
Use the Firmware Loading Tool (FLT) for this procedure.
1. Connect to the RTS port of the TEC.
2. Set Communications to 38400 baud.
3. Click the Identify button.
4. Browse to the folder where the new firmware is saved.
5. Double-click the firmware file and then click Load.
WCIS Procedure
1. Connect to the RTS port of the TEC.
2. From the Device menu, select Load TEC Firmware.
The Load TEC Firmware dialog box displays.
3. Click the Browse button.
4. Browse to the folder where the new firmware is saved.
5. Double-click the firmware file and then click Load.