Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Setting High Flow Setpoint
- Setting Low Flow Setpoint
- Setting ODP Display
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Damper Control
- Checkout of Damper
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Flashing Controller Firmware
Before You Begin
Setting Display Units
8
Siemens Industry, Inc. 140-1318
Restricted 2015-11-04
The air velocity sensor calibration cycle begins within three minutes of an application
start-up or initialization, depending on the controller’s address.
Setting Display Units
Set ENG UNITS to English or System International (SI) units (default is English units)
depending upon which unit (fpm or m/sec) you want displayed at the Operator Display
Panel.
NOTE:
All measurements entered during the start-up sequences may be entered as either
English or SI values (listed in parentheses after the English unit), depending upon
which unit has been selected using the Metric/English Units button on the appropriate
tool.
Testing the Operator Display Panel
Test the Operator Display Panel (ODP) as follows:
1. Set LAMP TEST to ON.
2. Verify that all visual display functions of the ODP appear and that the audible alarm
sounds continuously.
3. Set LAMP TEST to OFF.
Setting Duct Area
If provided, enter the duct area (sq ft or sq m) into DUCT AREA.
If you do not know the duct area, use the appropriate tool to calculate it, or use one of
the following equations to calculate it manually:
Area =
Round Duct
Rectangular Duct
Area in Sq. Ft.
(Dimensions in inches)
π x R
2
/144
(where R = radius of duct)
Width x Height/144
Area in Sq. M
(Dimensions in centimeters)
π x R
2
/10,000
(where R = radius of duct)
Width x Height/10,000
NOTE:
When entering the controller definition for a controller at the field panel, do not enter a
duct area. (Choose
N
for none when prompted for the duct shape.) This controller
does not send the value of air volume to the field panel in velocity (fpm). Instead, it
uses volume (cfm) so a conversion is not necessary.