Operating Instructions

Point Database
Siemens Building Technologies, Inc. 6-7
Address Descriptor Application Description
2603, 2611,
2612, 2613
90 OC V ALM LVL 2601, 2602,
2603, 2611,
2612, 2613
Ventilation alarm level in occupied mode.
91 UC V ALM LVL 2601, 2602,
2603, 2611,
2612, 2613
Ventilation alarm level in unoccupied mode.
{92} VENT ALM 2601, 2602,
2603, 2611,
2612, 2613
Alarm point indicates inadequate air change rate.
{93} SUP FLO STPT 2601, 2603,
2611, 2613
Desired value of the supply flow, chosen by the controller to achieve the
correct flow difference for the room.
{94} CAL AIR 2600, 2601,
2602, 2603,
2611, 2612, 2613
When the point is on, controller is calibrating the flow sensors. Turns off
automatically when done.
95 CAL SETUP 2600, 2601,
2602, 2603,
2611, 2612, 2613
Configuration setup code for the calibration sequence options.
96 CAL TIMER 2600, 2601,
2602, 2603,
2611, 2612, 2613
Time interval, in hours, between the calibration sequence initiations if a
timed calibration option is selected in the point CAL SETUP.
97 SUPDUCT AREA 2601, 2603,
2611, 2613
Cross-sectional area of the supply duct at the spot where the flow
sensor is installed.
98 LOOP TIME 2601, 2602,
2603, 2611,
2612, 2613
Time interval controls how often the LRC measures the room
temperature and calculates a new output value.
{99} ERROR STATUS 2600, 2601,
2602, 2603,
2611, 2612, 2613
Used to diagnose controller board failures.