MultiDrop operation
The SITRANS LC 500 transmitter supports MultiDrop Operation.
Burst mode
The SITRANS LC 500 transmitter does not support Burst Mode.
Units conversions
The Transmitter Variable #0 Units are in pF and cannot be changed.
The Transmitter Variable #1 Values may be set to any Units and Value with Command #140.
The Transmitter Variable Range Values may be read at any time with Command #141.
The value returned as Secondary Variable (S.V.) is the result of the following calculation:
TV1 = TV0 Dynamic Range Value in percent x ({TV#1}URV – {TV#1}LRV) + {TV#1}LRV.
This method provides a means of converting TV#0, which is always in pF, to alternative
units (level or volume).