User Manual
All important data 
at a glance
Switching/dimming actuator N 536D
•  One relay contact per output as 
a switching element
•  Contact rated current voltage  
AC 230 V
•  Contact rated frequency  
50 / 60 Hz
•  A control voltage output of DC...10 
V per channel for the control of 
dimmable electronic control gear
•  Manual control function for each 
channel on the device for switching 
and dimming and activating direct 
operation
•  Maintenance-free terminals for 
connecting and looping through 
solid, stranded, and fine-stranded 
conductors, 0.5 to 2.5 mm
2
•  At least one phase connection 
terminal per output
•  Operation of electronics via bus 
voltage
•  Integrated bus coupler, bus connec-
tion via bus terminal block
•  Red LED for displaying the activation 
of address mode and readiness for 
operation
•  Housing Plastic; color:  
RAL 7035 (light gray); N-dimension
•  DIN rail-mounted device for installa-
tion on rail TH35 DIN EN 60715
•  Protection type: IP 20
•  Switching construction site function
•  Object for monitoring device 
functionality
•  Object for targeted call-up of status 
values 
Control functions
•  Selectable operating mode: normal 
mode, 1- or 2-level timer mode, 
flashing
•  Configurable control value input for 
ON/OFF switching depending on 
threshold values
•  Configurable on/off switch delay
•  Central switching with separately 
configurable on/off delay
•  Logic operations (AND, OR, NOT 
AND, EXCLUSIVE OR, NOT OR, 
FILTER, TRIGGER)
•  Switching the output on/off via 
dimming brighter/darker
•  Dimming curves for optimization of 
dimming behavior of lamps configu-
rable
•  Maximum and minimum dimming 
values configurable via parameters 
and object 
– night mode object for time-limited 
switching on of the output at 
night can be added
•  Retriggering of ON time (ON time 
extension) during timer mode up to 
a configurable maximum extension 
with repeated (2x, 3x, 4x, 5x) 
retriggering
•  Integrated 8-bit scene control with 
up to 8 scene assignments per 
output
•  Configurable switching state for bus 
voltage failure and starting value of 
the switching object for when bus 
voltage is recovered
•  Addable night mode object for 
time-limited switch-on of the 
output, i.e., the lighting 
Override functions
•  Manual override ON
•  Permanent OFF
•  Lock mode
•  Central override
•  Forced switch-on/off 
Diagnostic functions:
•  Counting of operating hours with 
threshold monitoring
•  Counting of switching cycles with 
threshold monitoring
•  Status messages
Shared 
characteristics
Functions 
per device
Type Design OC Order no. PE  
(ST, SZ, M)
PKG/ 
VPE
PG Price 
(€)
N 536D31 Switching/dimming actuator 4 x AC 230 V, 10 AX, 
1…10 V
A 5WG1536-1DB31 1 1
N 536D51 Switching/dimming actuator 8 x AC 230 V, 10 AX, 
1…10 V
A 5WG1536-1DB51 1 1