Damping Filter (2.2.4.)
The time constant for the damping filter. The damping filter smooths out the response to a
sudden change in level. This is an exponential filter and the engineering unit is always in
seconds [see Damping (Page 230) for more detail].
Values Range: 0 to 100.000 s
Default: 10.000 s
Calibration (2.3.)
Note
We recommend using the Quick Start wizard to configure the device.
Low Calibration Pt. (2.3.1.)
Distance from sensor reference point
1)
to Low Calibration Point. Units are defined in Units
(2.2.1.)
Values Range: 0 to 20 m. Default: 20.00 m
Related parameters Units (2.2.1.)
Far Range (2.8.2.)
1)
The point from which level measurement is referenced, see Threaded Horn Antenna with
extension (Page 181), Flanged Horn with extension (Page 186), and PTFE Flanged
encapsulated antenna (3"/DN80/80A sizes and larger) (Page 192).
High Calibration Pt. (2.3.2.)
Distance from sensor reference point
1)
to High Calibration Point. Units are defined in Units
(2.2.1.).
Values Range: 0 to 20 m. Default 0.00 m
Related parameters Units (2.2.1.)
Near Range (2.8.1.)
When setting the High Calibration Point value, note that echoes are ignored within Near Range
(2.8.1.).
1)
The value produced by the echo processing which represents the distance from sensor
reference point to the target. [see Threaded Horn Antenna with extension (Page 181), Flanged
Horn with extension (Page 186), and PTFE Flanged encapsulated antenna (3"/DN80/80A
sizes and larger) (Page 192)].
Parameter reference
SITRANS LR250 with mA/HART
110 Operating Instructions, 10/2019, A5E32220602-AG