Vessel Shape LCD DISPLAY/ Description Also required
$
/
PARABOLIC ENDS/
Parabolic end horizontal
cylinder
Maximum volume, di‐
mension A, dimension L
LINEAR TABLE
a)
/ Lineari‐
zation table (level/volume
breakpoints)
Maximum volume, ta‐
bles 1-32 level and vol‐
ume breakpoints
a)
Linearization Table must be selected in order for level/volume values [see Table 1-8 (2.7.2.)] to be
transferred.
Maximum Volume (2.7.1.2.)
The maximum volume of the vessel. Enter the vessel volume corresponding to High Calibration
Point. For example, if your maximum vessel volume is 8000 L, enter a value of 8000. Volume
units are defined by the user but are not explicitly stated or shown in the SITRANS LR250.
Values Range: 0.0 to 99999 m
Default: 100.0
Related Parameters Low Calibration Pt. (2.3.1.)
High Calibration Pt. (2.3.2.)
Vessel Shape (2.7.1.1.)
Vessel Dimension A (2.7.1.3.)
The height of the vessel bottom when the bottom is conical, pyramidal, parabolic, spherical, or
flat -sloped. If the vessel is horizontal with parabolic ends, the depth of the end. See Vessel
Shape (2.7.1.1.) for an illustration.
Values Range: 0.0 to 99.999 m
Default: 0.0
Related Parameters Units (2.2.1.)
Vessel Shape (2.7.1.1.)
Parameter reference
SITRANS LR250 with mA/HART