Operating Instructions
Table Of Contents
- SITRANS LR250 with mA/HART
- Legal information - Warning notice system
- Table of contents
- 1 Introduction
- 2 Safety information
- 3 Description
- 4 Installing/mounting
- 5 Connecting
- 6 Commissioning
- 7 Remote operation
- 7.1 Operating via SIMATIC PDM
- 7.1.1 Functions in SIMATIC PDM
- 7.1.2 Initial setup
- 7.1.3 Updating the Electronic Device Description (EDD)
- 7.1.4 Quick Start Wizard via SIMATIC PDM
- 7.1.5 Changing parameter settings using SIMATIC PDM
- 7.1.6 Parameters accessed via pull-down menus
- 7.1.6.1 Echo profile utilities
- 7.1.6.2 Echo profile
- 7.1.6.3 View saved echo profiles
- 7.1.6.4 TVT Shaper
- 7.1.6.5 Auto false echo suppression
- 7.1.6.6 Echo setup
- 7.1.6.7 Maintenance
- 7.1.6.8 Select analog output
- 7.1.6.9 Self test
- 7.1.6.10 Loop test
- 7.1.6.11 Configuration flag reset
- 7.1.6.12 Master reset
- 7.1.6.13 Wear
- 7.1.6.14 HART Communication
- 7.1.6.15 Process variables
- 7.1.6.16 Trend
- 7.1.6.17 Device status
- 7.1.6.18 Update
- 7.1.6.19 Security
- 7.2 Operating via AMS Device Manager
- 7.3 Operating via FDT (Field Device Tool)
- 7.1 Operating via SIMATIC PDM
- 8 Parameter reference
- 9 Service and maintenance
- 10 Diagnosing and troubleshooting
- 11 Technical data
- 12 Dimension drawings
- 12.1 Universal polymeric flange
- 12.2 Aluminum horn antenna
- 12.3 Mounting bracket
- 12.4 Aluminum horn with polypropylene lens antenna and polymeric flange
- 12.5 Stainless steel threaded horn antenna
- 12.6 Stainless steel threaded horn antenna with extension
- 12.7 Stainless steel flanged horn antenna
- 12.8 Stainless steel flanged horn antenna with extension
- 12.9 PTFE Flanged encapsulated antenna (2"/DN50/50A sizes only)
- 12.10 PTFE Flanged encapsulated antenna (3"/DN80/80A sizes and larger)
- 12.11 Hygienic encapsulated antenna (2" ISO 2852 sanitary clamp)
- 12.12 Hygienic encapsulated antenna (3" ISO 2852 sanitary clamp)
- 12.13 Hygienic encapsulated antenna (4" ISO 2852 sanitary clamp)
- 12.14 Hygienic encapsulated antenna (DN50 nozzle/slotted nut to DIN 11851)
- 12.15 Hygienic encapsulated antenna (DN80 nozzle/slotted nut to DIN 11851)
- 12.16 Hygienic encapsulated antenna (DN100 nozzle/slotted nut to DIN 11851)
- 12.17 Hygienic encapsulated antenna (DN50 aseptic slotted nut to DIN 11864-1)
- 12.18 Hygienic encapsulated antenna (DN80 aseptic slotted nut to DIN 11864-1)
- 12.19 Hygienic encapsulated antenna (DN100 aseptic slotted nut to DIN 11864-1)
- 12.20 Hygienic encapsulated antenna (DN50 aseptic flange to DIN 11864-2)
- 12.21 Hygienic encapsulated antenna (DN80 aseptic flange to DIN 11864-2)
- 12.22 Hygienic encapsulated antenna (DN100 aseptic flange to DIN 11864-2)
- 12.23 Hygienic encapsulated antenna (DN50 aseptic clamp to DIN 11864-3)
- 12.24 Hygienic encapsulated antenna (DN80 aseptic clamp to DIN 11864-3)
- 12.25 Hygienic encapsulated antenna (DN100 aseptic clamp to DIN 11864-3)
- 12.26 Hygienic encapsulated antenna (Tuchenhagen Type N)
- 12.27 Hygienic encapsulated antenna (Tuchenhagen Type F)
- 12.28 Threaded PVDF antenna
- 12.29 Threaded connection markings
- 12.30 Raised-Face flange
- 12.31 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna
- 12.32 Flat-Face flange
- 12.33 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2
- 12.34 Process connection tag (pressure rated versions)
- A Appendix A: Technical reference
- A.1 Principles of operation
- A.2 Echo Processing
- A.3 Analog Output
- A.4 Maximum Process Temperature Chart
- A.5 Process Pressure/Temperature derating curves
- A.5.1 Pressure Equipment Directive, PED, 14/68/EU
- A.5.2 Stainless steel horn antenna
- A.5.3 Stainless steel flanged horn antenna
- A.5.4 PTFE flanged encapsulated antenna
- A.5.5 Aluminum horn, with polypropylene lens antenna version with polypropylene flange
- A.5.6 PVDF antenna
- A.5.7 Hygienic encapsulated antenna
- A.6 Loop power
- A.7 Startup behavior
- B Appendix B: HART communications
- C Appendix C: Certificates and support
- 13 List of abbreviations
- 14 LCD menu structure
- Glossary
- Index
Position Detect (2.8.4.2.)
Defines where on the echo the distance measurement is determined.
Options Center
* Hybrid (Center and CLEF)
CLEF (Constrained Leading Edge Fit)
Related parameters CLEF Range (2.8.4.4.)
If the vessel bottom is being reported as the level instead of the actual material level (at low level
conditions), or if the dielectric constant of the liquid to be monitored is less than 3, we
recommend setting Position Detect to Hybrid and CLEF Range (2.8.4.4.) to 0.5 m (1.64 ft).
Echo Threshold (2.8.4.3.)
Sets the minimum echo confidence that the echo must meet in order to prevent a Loss of Echo
condition and the expiration of the Fail-safe (LOE) timer. When Confidence (2.8.6.1.)
exceeds Echo Threshold (2.8.4.3.), the echo is accepted as a valid echo and is evaluated.
Values Range: 0 to 99
Default: 5
Related Parameters LOE Timer (2.5.2.)
CLEF Range (2.8.4.4.)
Note
CLEF Range is referenced from Far range.
The CLEF algorithm is used mainly to allow correct level reporting for low dK materials which
may otherwise cause an incorrect reading in an empty or almost empty vessel.
It is used from Low Calibration Point (process empty level ) up to the level defined by CLEF
Range (see illustration below). Above that point the Center algorithm is used. For more detail
see CLEF Range (Page 227).
Values Range: 0 to 20 m (0 to 65.6 ft)
Default: 0.0 m
Related parameters Position Detect (2.8.4.2.)
Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG 123