Operating Instructions
Table Of Contents
- SITRANS LR250 with mA/HART
- Legal information - Warning notice system
- Table of contents
- 1 Introduction
- 2 Safety information
- 3 Description
- 4 Installing/mounting
- 5 Connecting
- 6 Commissioning
- 7 Remote operation
- 7.1 Operating via SIMATIC PDM
- 7.1.1 Functions in SIMATIC PDM
- 7.1.2 Initial setup
- 7.1.3 Updating the Electronic Device Description (EDD)
- 7.1.4 Quick Start Wizard via SIMATIC PDM
- 7.1.5 Changing parameter settings using SIMATIC PDM
- 7.1.6 Parameters accessed via pull-down menus
- 7.1.6.1 Echo profile utilities
- 7.1.6.2 Echo profile
- 7.1.6.3 View saved echo profiles
- 7.1.6.4 TVT Shaper
- 7.1.6.5 Auto false echo suppression
- 7.1.6.6 Echo setup
- 7.1.6.7 Maintenance
- 7.1.6.8 Select analog output
- 7.1.6.9 Self test
- 7.1.6.10 Loop test
- 7.1.6.11 Configuration flag reset
- 7.1.6.12 Master reset
- 7.1.6.13 Wear
- 7.1.6.14 HART Communication
- 7.1.6.15 Process variables
- 7.1.6.16 Trend
- 7.1.6.17 Device status
- 7.1.6.18 Update
- 7.1.6.19 Security
- 7.2 Operating via AMS Device Manager
- 7.3 Operating via FDT (Field Device Tool)
- 7.1 Operating via SIMATIC PDM
- 8 Parameter reference
- 9 Service and maintenance
- 10 Diagnosing and troubleshooting
- 11 Technical data
- 12 Dimension drawings
- 12.1 Universal polymeric flange
- 12.2 Aluminum horn antenna
- 12.3 Mounting bracket
- 12.4 Aluminum horn with polypropylene lens antenna and polymeric flange
- 12.5 Stainless steel threaded horn antenna
- 12.6 Stainless steel threaded horn antenna with extension
- 12.7 Stainless steel flanged horn antenna
- 12.8 Stainless steel flanged horn antenna with extension
- 12.9 PTFE Flanged encapsulated antenna (2"/DN50/50A sizes only)
- 12.10 PTFE Flanged encapsulated antenna (3"/DN80/80A sizes and larger)
- 12.11 Hygienic encapsulated antenna (2" ISO 2852 sanitary clamp)
- 12.12 Hygienic encapsulated antenna (3" ISO 2852 sanitary clamp)
- 12.13 Hygienic encapsulated antenna (4" ISO 2852 sanitary clamp)
- 12.14 Hygienic encapsulated antenna (DN50 nozzle/slotted nut to DIN 11851)
- 12.15 Hygienic encapsulated antenna (DN80 nozzle/slotted nut to DIN 11851)
- 12.16 Hygienic encapsulated antenna (DN100 nozzle/slotted nut to DIN 11851)
- 12.17 Hygienic encapsulated antenna (DN50 aseptic slotted nut to DIN 11864-1)
- 12.18 Hygienic encapsulated antenna (DN80 aseptic slotted nut to DIN 11864-1)
- 12.19 Hygienic encapsulated antenna (DN100 aseptic slotted nut to DIN 11864-1)
- 12.20 Hygienic encapsulated antenna (DN50 aseptic flange to DIN 11864-2)
- 12.21 Hygienic encapsulated antenna (DN80 aseptic flange to DIN 11864-2)
- 12.22 Hygienic encapsulated antenna (DN100 aseptic flange to DIN 11864-2)
- 12.23 Hygienic encapsulated antenna (DN50 aseptic clamp to DIN 11864-3)
- 12.24 Hygienic encapsulated antenna (DN80 aseptic clamp to DIN 11864-3)
- 12.25 Hygienic encapsulated antenna (DN100 aseptic clamp to DIN 11864-3)
- 12.26 Hygienic encapsulated antenna (Tuchenhagen Type N)
- 12.27 Hygienic encapsulated antenna (Tuchenhagen Type F)
- 12.28 Threaded PVDF antenna
- 12.29 Threaded connection markings
- 12.30 Raised-Face flange
- 12.31 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna
- 12.32 Flat-Face flange
- 12.33 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2
- 12.34 Process connection tag (pressure rated versions)
- A Appendix A: Technical reference
- A.1 Principles of operation
- A.2 Echo Processing
- A.3 Analog Output
- A.4 Maximum Process Temperature Chart
- A.5 Process Pressure/Temperature derating curves
- A.5.1 Pressure Equipment Directive, PED, 14/68/EU
- A.5.2 Stainless steel horn antenna
- A.5.3 Stainless steel flanged horn antenna
- A.5.4 PTFE flanged encapsulated antenna
- A.5.5 Aluminum horn, with polypropylene lens antenna version with polypropylene flange
- A.5.6 PVDF antenna
- A.5.7 Hygienic encapsulated antenna
- A.6 Loop power
- A.7 Startup behavior
- B Appendix B: HART communications
- C Appendix C: Certificates and support
- 13 List of abbreviations
- 14 LCD menu structure
- Glossary
- Index
Auto False Echo Suppression (2.8.7.1.)
Used together with Auto False Echo Suppression Range (2.8.7.2.) to screen out false echoes
in a vessel with known obstructions. A ’learned TVT’ (time varying threshold) replaces the
default TVT over a specified range. See Auto False Echo Suppression (Page 228) for a more
detailed explanation.
Note
● Make sure material level is below all known obstructions when Auto False Echo
Suppression is used to learn the echo profile. (An empty or almost empty vessel is
recommended.)
● Note the distance to material level when Auto False Echo learns the environment. Set Auto
False Echo Suppression Range to a shorter distance to avoid the material echo being
screened out.
● Set Auto False Echo Suppression and Auto False Echo Suppression Range during startup,
if possible.
● If the vessel contains an agitator it should be running.
● Before adjusting these parameters, rotate the instrument for best signal (lower false-echo
amplitude).
Before Auto False Echo Suppression
1
2
3
4
5
/HYHOGE
3URILOH>G%@
'LVWDQFH>P@
① TVT Hover Level ④ echo marker
② default TVT ⑤ material level
③ false echo
1. Determine Auto False Echo Suppression Range. Measure the actual distance from the
sensor reference point to the material surface using a rope or tape measure.
2. Subtract 0.5 m (20") from this distance, and use the resulting value.
3. Go to Auto False Echo Suppression Range (2.8.7.2.) and enter the value calculated in
step 2.
Parameter reference
SITRANS LR250 with mA/HART
126 Operating Instructions, 10/2019, A5E32220602-AG