Operating Instructions
Table Of Contents
- SITRANS LR250 with mA/HART
- Legal information - Warning notice system
- Table of contents
- 1 Introduction
- 2 Safety information
- 3 Description
- 4 Installing/mounting
- 5 Connecting
- 6 Commissioning
- 7 Remote operation
- 7.1 Operating via SIMATIC PDM
- 7.1.1 Functions in SIMATIC PDM
- 7.1.2 Initial setup
- 7.1.3 Updating the Electronic Device Description (EDD)
- 7.1.4 Quick Start Wizard via SIMATIC PDM
- 7.1.5 Changing parameter settings using SIMATIC PDM
- 7.1.6 Parameters accessed via pull-down menus
- 7.1.6.1 Echo profile utilities
- 7.1.6.2 Echo profile
- 7.1.6.3 View saved echo profiles
- 7.1.6.4 TVT Shaper
- 7.1.6.5 Auto false echo suppression
- 7.1.6.6 Echo setup
- 7.1.6.7 Maintenance
- 7.1.6.8 Select analog output
- 7.1.6.9 Self test
- 7.1.6.10 Loop test
- 7.1.6.11 Configuration flag reset
- 7.1.6.12 Master reset
- 7.1.6.13 Wear
- 7.1.6.14 HART Communication
- 7.1.6.15 Process variables
- 7.1.6.16 Trend
- 7.1.6.17 Device status
- 7.1.6.18 Update
- 7.1.6.19 Security
- 7.2 Operating via AMS Device Manager
- 7.3 Operating via FDT (Field Device Tool)
- 7.1 Operating via SIMATIC PDM
- 8 Parameter reference
- 9 Service and maintenance
- 10 Diagnosing and troubleshooting
- 11 Technical data
- 12 Dimension drawings
- 12.1 Universal polymeric flange
- 12.2 Aluminum horn antenna
- 12.3 Mounting bracket
- 12.4 Aluminum horn with polypropylene lens antenna and polymeric flange
- 12.5 Stainless steel threaded horn antenna
- 12.6 Stainless steel threaded horn antenna with extension
- 12.7 Stainless steel flanged horn antenna
- 12.8 Stainless steel flanged horn antenna with extension
- 12.9 PTFE Flanged encapsulated antenna (2"/DN50/50A sizes only)
- 12.10 PTFE Flanged encapsulated antenna (3"/DN80/80A sizes and larger)
- 12.11 Hygienic encapsulated antenna (2" ISO 2852 sanitary clamp)
- 12.12 Hygienic encapsulated antenna (3" ISO 2852 sanitary clamp)
- 12.13 Hygienic encapsulated antenna (4" ISO 2852 sanitary clamp)
- 12.14 Hygienic encapsulated antenna (DN50 nozzle/slotted nut to DIN 11851)
- 12.15 Hygienic encapsulated antenna (DN80 nozzle/slotted nut to DIN 11851)
- 12.16 Hygienic encapsulated antenna (DN100 nozzle/slotted nut to DIN 11851)
- 12.17 Hygienic encapsulated antenna (DN50 aseptic slotted nut to DIN 11864-1)
- 12.18 Hygienic encapsulated antenna (DN80 aseptic slotted nut to DIN 11864-1)
- 12.19 Hygienic encapsulated antenna (DN100 aseptic slotted nut to DIN 11864-1)
- 12.20 Hygienic encapsulated antenna (DN50 aseptic flange to DIN 11864-2)
- 12.21 Hygienic encapsulated antenna (DN80 aseptic flange to DIN 11864-2)
- 12.22 Hygienic encapsulated antenna (DN100 aseptic flange to DIN 11864-2)
- 12.23 Hygienic encapsulated antenna (DN50 aseptic clamp to DIN 11864-3)
- 12.24 Hygienic encapsulated antenna (DN80 aseptic clamp to DIN 11864-3)
- 12.25 Hygienic encapsulated antenna (DN100 aseptic clamp to DIN 11864-3)
- 12.26 Hygienic encapsulated antenna (Tuchenhagen Type N)
- 12.27 Hygienic encapsulated antenna (Tuchenhagen Type F)
- 12.28 Threaded PVDF antenna
- 12.29 Threaded connection markings
- 12.30 Raised-Face flange
- 12.31 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna
- 12.32 Flat-Face flange
- 12.33 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2
- 12.34 Process connection tag (pressure rated versions)
- A Appendix A: Technical reference
- A.1 Principles of operation
- A.2 Echo Processing
- A.3 Analog Output
- A.4 Maximum Process Temperature Chart
- A.5 Process Pressure/Temperature derating curves
- A.5.1 Pressure Equipment Directive, PED, 14/68/EU
- A.5.2 Stainless steel horn antenna
- A.5.3 Stainless steel flanged horn antenna
- A.5.4 PTFE flanged encapsulated antenna
- A.5.5 Aluminum horn, with polypropylene lens antenna version with polypropylene flange
- A.5.6 PVDF antenna
- A.5.7 Hygienic encapsulated antenna
- A.6 Loop power
- A.7 Startup behavior
- B Appendix B: HART communications
- C Appendix C: Certificates and support
- 13 List of abbreviations
- 14 LCD menu structure
- Glossary
- Index
Acknowledge Status (4.5.8.)
Indicates which level of maintenance reminder has been acknowledged.
In SIMATIC PDM, open the menu View – Device Status, click on the Maintenance tab and
check the Calibration Schedule Status window.
Acknowledge (4.5.9.)
Acknowledges the current maintenance reminder.
To acknowledge a reminder via SIMATIC PDM:
1. Open the menu View – Device Status and click on the Maintenance tab.
2. In the Service Schedule Status section, click on Acknowledge Warnings.
To acknowledge a reminder via the handheld programmer:
1. Press RIGHT
arrow twice to open parameter view and activate Edit Mode.
2. Press RIGHT arrow to acknowledge the reminder.
Manufacture Date (4.6.)
Read only. The date of manufacture of the SITRANS LR250 (yy mm dd).
Powered Hours (4.7.)
Read only. Displays the number of hours the unit has been powered up since manufacture.
In SIMATIC PDM, open the menu Device – Wear.
Power-on Resets (4.8.)
Read only. The number of power cycles that have occurred since manufacture.
In SIMATIC PDM, open the menu Device – Wear.
LCD Fast Mode (4.9.)
Note
● LCD Fast Mode takes effect only after 30 minutes of inactivity. (Each time the device is
powered up, a further 30 minutes of inactivity is required.)
● LCD Fast Mode affects Measurement mode only; it has no effect on Navigation mode.
Enables a faster rate of measurement from the device by disabling most of the display area.
Only the bar graph will be refreshed when LCD Fast Mode is set to ON.
Values ON or OFF
Default: OFF
Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG 145