Sets the device address or poll ID on a HART network. Any address other than 0 will cause the
output current to be a fixed value, and the current will not indicate the reading.
Values Range: 0 to 15
Default: 0
To set Device Address via SIMATIC PDM:
Open the project in Process Device Network View then right-click on the device.
Go to Object Properties > Connection to access the field Short Address.
Security (6.)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.
Remote Access (6.1.)
Access Control (6.1.1.)
Note
If access control is changed to limit remote access, it can only be reset via the handheld
programmer.
Enables/disables the read/write access to parameters via remote communications.
Options Read only No changes are permitted via remote commu‐
nications.
* Read Write Changes are permitted.
Restricted Sets the status to Read only, with the potential
for another HART device to change this pa‐
rameter only, via remote communications.
Local Access (6.2.)
Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG 147