Diagnosing and troubleshooting
10
10.1 Communication troubleshooting
1. Check the following:
There is power at the device.
The LCD shows the relevant data.
The device can be programmed using the handheld programmer.
If any fault codes are being displayed see General Fault Codes (Page 160) for a detailed
list.
2. Verify that the wiring connections are correct.
3. See the table below for specific symptoms.
Symptom Corrective action
The device cannot be programmed via the
handheld programmer.
Ensure Write Protect (6.2.1.) is set to the unlock value.
You try to set a SITRANS LR250 parame‐
ter via remote communications but the pa‐
rameter remains unchanged.
Ensure Write Protect (6.2.1.) is set to the unlock value,
then try setting the parameter via the handheld
programmer.
Ensure Access Control (6.1.1.) is set to Read/ Write.
Some parameters can be changed only when the
device is not scanning. Try pressing Mode to put
the device into PROGRAM mode.
If you continue to experience problems go to our website and check the FAQs for SITRANS
LR250:
Product page (http://www.siemens.com/LR250), or contact your Siemens representative.
10.2 Device status icons
Icon Priority
Level
Meaning
1
Maintenance alarm
Measurement values are not valid
2
Maintenance warning: maintenance demanded immediately
Measured signal still valid
3
Maintenance required
Measured signal still valid
1
Process value has reached an alarm limit
SITRANS LR250 with mA/HART