Symptom Cause Action
Display shows
6/2(
antenna malfunction:
temperature too high
physical damage
excessive foam
multiple echoes
check Current Internal Temperature (3.2.1.)
use foam deflector or stillpipe
relocate
use a defoamer
set Algorithm (2.8.4.1.) to F (First echo)
Reading does not
change, but the level
does
SITRANS LR250 processing
wrong echo, for example, vessel
wall, or structural member
re-locate SITRANS LR250
check nozzle for internal burrs or welds
rotate device 90°
use Auto False Echo Suppression (2.8.7.1.)
if necessary: see Auto False Echo Suppression (Page 228).
Measurement is con‐
sistently off by a con‐
stant amount
setting for Low Calibration Pt.
(2.3.1.) not correct
setting for Sensor Offset
(2.3.3.) not correct
check distance from sensor reference point to Low
Calibration Pt. (2.3.1.)
check Sensor Offset (2.3.3.)
Screen blank power error
check nameplate rating against voltage supply
check power wiring or source
too much load resistance
change barrier type, or
remove something from the loop, or
increase supply voltage
reduce wire distance or use larger gage wire
Reading erratic echo confidence weak
refer to Confidence (2.8.6.1.)
use Auto False Echo Suppression (2.8.7.1.) and Auto False
Echo Suppression Range (2.8.7.2.)
use foam deflector or stillpipe
liquid surface vortexed
decrease Fill Rate per Minute (2.4.2.)
relocate device to side pipe
increase confidence threshold in Echo Threshold (2.8.4.3.)
material filling
Re-locate SITRANS LR250
Reading response slow Fill Rate per Minute (2.4.2.) set‐
ting incorrect
increase measurement response if possible
Reads correctly but oc‐
casionally reads high
when vessel is not full
detecting close range echo
build up near top of vessel or
nozzle
nozzle problem
clean the antenna
use Auto False Echo Suppression (2.8.7.1.) and Auto False
Echo Suppression Range (2.8.7.2.)
Level reading lower
than actual material
level
material is within Near Range
zone
multiple echoes processed
decrease Near Range (2.8.1.) (minimum value depends on
antenna type)
raise SITRANS LR250
ensure Algorithm (2.8.4.1.) is set to F (First echo)
vessel near empty and low dK
material
ensure Material (2.2.3.) selection is LIQUID LOW DK
set Position Detect (2.8.4.2.) to Hybrid
set CLEF Range (2.8.4.4.) to 0.5 m
Diagnosing and troubleshooting
10.4 Operation troubleshooting
SITRANS LR250 with mA/HART
164 Operating Instructions, 10/2019, A5E32220602-AG