6.2.3 Programming
Note
While the device is in PROGRAM mode the output remains fixed and does not respond to
changes in the device.
The device automatically returns to Measurement mode after a period of inactivity in
PROGRAM mode (between 15 seconds and 2 minutes, depending on the menu level).
Change parameter settings and set operating conditions to suit your specific application. For
remote operation see Operating via SIMATIC PDM (Page 63) or Operating via AMS Device
Manager (Page 83).
Parameter menus
Note
For the complete list of parameters with instructions, see Parameter Reference (Page 107).
Parameters are identified by name and organized into function groups. See LCD menu
structure (Page 255).
1. QUICK START
2. SETUP
2.1. DEVICE
............
2.7. LINEARIZATION
2.7.1. VOLUME
2.7.1.1. VESSEL SHAPE
1. Enter PROGRAM mode
Point the programmer at the display from a maximum distance of 300 mm (1 ft).
RIGHT arrow activates PROGRAM mode and opens menu level 1.
Mode opens the menu level last displayed in PROGRAM mode within the last 10
minutes, or menu level 1 if power has been cycled since then.
2
1
3
Commissioning
6.2 Operating via the handheld programmer
SITRANS LR250 with mA/HART
50 Operating Instructions, 10/2019, A5E32220602-AG