Distance from Sensor reference point to High Calibration Point: usually process full level. (See
Operation for an illustration.)
Values Range: 0.00 to 20.00 m
Wizard complete
Options BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start Wiz menu when Quick
Start is successfully completed.)
Press DOWN arrow (Finish). Then press LEFT arrow to return to Measurement mode.
SITRANS LR250 is now ready to operate.
6.2.3.2 Auto False Echo Suppression
If you have a vessel with known obstructions, we recommend using Auto False Echo
Suppression to prevent false echo detection. See TVT setup (2.8.7.) for instructions.
This feature can also be used if the display shows a false high level, or the reading is fluctuating
between the correct level and a false high level.
6.2.3.3 Requesting an Echo Profile
In PROGRAM mode, navigate to: Level Meter > 3. > 3.1.
Press RIGHT arrow to request a profile.
6
9
8
7
54321
(FKRDPSOLWXGHLQG%
10
11
Commissioning
6.2 Operating via the handheld programmer
SITRANS LR250 with mA/HART
56 Operating Instructions, 10/2019, A5E32220602-AG