Operating Instructions

Table Of Contents
Parameter type Parameter No./Name Options/
Values
Function
Independent pa‐
rameters
Vessel Shape (2.7.1.1.) PARABOLIC
ENDS
Defines vessel shape.
Maximum Volume (2.7.1.2.) 8000 8000 liters
Vessel Dimension A (2.7.1.3.) 0.8 0.8 m (2.62 ft)
Vessel Dimension L (2.7.1.4.) 6 6 m (19.68 ft)
LOE Timer (2.5.2.) 2 2 minutes
Material Level (2.5.1.) HI Fail-safe level set to High
Return to Measurement: press Mode to start normal operation.
6.3.3 Application with stillpipe
Note
Near Range (2.8.1.) (Blanking) will be set at the factory. Check the process connection tag
for specific values.
Suitable pipe diameters are 40 mm (1.5") to 100 mm (4").
The pipe diameter must be matched with the antenna size. Use the largest antenna size that
will fit the stillpipe/bypass pipe. See Dimensions (Page 175).
See Mounting on a Stillpipe or Bypass Pipe (Page 29) for installation guidelines.
This application is to obtain a level measurement and corresponding 4 to 20 mA output
proportional to the oil level in a fuel storage vessel.
Low Calibration Pt. is 5 m (16.5 ft) from the sensor reference point.
High Calibration Pt. is 0.5 m (1.65 ft) from the sensor reference point.
The stillpipe inside diameter is 50 mm (1.96").
The maximum rate of filling or emptying is about 0.1 m (4")/min.
1
3
4
6
5
7
2
sensor reference point 5 m
high calibration point 50 mm I.D.
0.5 m low calibration point
vent hole
Commissioning
6.3 Application examples
SITRANS LR250 with mA/HART
60 Operating Instructions, 10/2019, A5E32220602-AG