SITRANS L Radar transmitters SITRANS LR260 with mA/HART Operating Instructions 7ML5427 11/2019 A5E32337683-AD Introduction 1 Safety notes 2 Description 3 Installing/mounting 4 Connecting 5 Commissioning 6 Operating 7 Parameter reference 8 Service and maintenance 9 Diagnosing and troubleshooting 10 Technical data 11 Dimension drawings 12 Application examples 13 Appendix A: Technical reference A Appendix B: HART Communications B Product documentation and support C List of
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Table of contents 1 2 3 4 Introduction.................................................................................................................................................11 1.1 Purpose of this documentation...............................................................................................11 1.2 Document history ...................................................................................................................11 1.3 FW Revision history .......................
Table of contents 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.8 4.3.9 5 6 4 Nozzle location.......................................................................................................................26 Orientation in a vessel with obstructions................................................................................27 Stainless steel Easy Aimer.....................................................................................................28 Aluminum aimer flanges.......................
Table of contents 6.3.2 7 Operating....................................................................................................................................................59 7.1 7.1.1 7.1.1.1 7.1.1.2 7.1.1.3 7.1.1.4 7.1.2 7.1.2.1 7.1.2.2 7.1.2.3 7.1.2.4 7.1.3 7.1.4 7.1.5 7.1.5.1 7.1.5.2 7.1.5.3 7.1.5.4 7.1.5.5 7.1.5.6 7.1.5.7 7.1.5.8 7.1.5.9 7.1.5.10 7.1.5.11 7.1.5.12 7.1.5.13 7.1.5.14 7.1.5.15 7.1.5.16 8 Level application example..............................................................
Table of contents 8.5.4 8.5.5 8.5.6 8.5.7 8.5.8 8.5.9 8.5.10 8.5.11 8.5.12 8.5.13 8.5.14 8.5.15 8.5.16 8.5.16.1 8.5.16.2 8.5.16.3 8.5.16.4 8.5.16.5 8.5.16.6 8.5.16.7 8.5.16.8 8.5.17 8.5.18 8.5.19 8.5.20 8.5.21 8.5.22 8.5.23 8.5.24 8.5.25 8.5.26 8.5.27 8.5.28 8.5.29 8.5.30 8.5.31 8.5.32 8.5.33 8.5.34 8.5.35 8.5.36 8.5.37 8.5.37.1 8.5.38 8.5.39 8.5.40 8.5.41 8.5.42 8.5.43 8.5.44 8.5.45 8.5.46 6 Hardware Revision (HARDWARE REV.) (2.1.3.)...................................................................
Table of contents 8.5.47 8.5.48 8.5.49 8.5.50 Fail-safe (2.4.) ........................................................................................................................94 Fail-safe Timer (2.4.1.)...........................................................................................................94 Fail-safe Material Level (FAILSAFE MAT. LE) (2.4.2.) ..........................................................95 Fail-safe Level (2.4.4.) ...................................................
Table of contents 9 10 11 8 8.7.21 8.7.22 8.7.23 8.7.24 8.7.25 8.7.26 8.7.27 Maintenance Required Limit (MAINT. REQ. LIMIT) (4.17.3.) ..............................................109 Maintenance Demanded Limit (MAINT. DEM. LIMIT) (4.17.4.) ...........................................109 Maintenance Alert Activation (4.17.5.) .................................................................................109 Total Calibration Interval (TOTAL CALIB. INTRV.) (4.17.6.)....................................
Table of contents 12 13 11.7 Approvals data .....................................................................................................................129 11.8 Programmer data - 7ML1930-1BK .......................................................................................129 Dimension drawings .................................................................................................................................131 12.1 Stainless steel aimer version ..........................
Table of contents A.12.2 A.12.3 B C D Appendix B: HART Communications........................................................................................................165 B.1 HART communications ........................................................................................................165 B.2 SIMATIC PDM......................................................................................................................165 B.3 HART Electronic Device Description (EDD).............
1 Introduction Note This manual applies to the SITRANS LR260 mA/HART version only. HART® is a registered trademark of the HART Communication Foundation. 1.1 Purpose of this documentation These instructions contain all information required to commission and use the device. Read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation.
Introduction 1.6 Security information 1.4 Industrial use note NOTICE Use in a domestic environment This Class B Group 1 equipment is intended for use in industrial areas. In a domestic environment this device may cause radio interference. 1.5 Checking the consignment 1. Check the packaging and the delivered items for visible damages. 2. Report any claims for damages immediately to the shipping company. 3. Retain damaged parts for clarification. 4.
Introduction 1.8 Notes on warranty To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under https://www.siemens.com/industrialsecurity (https://www.siemens.com/industrialsecurity). 1.7 Transportation and storage To guarantee sufficient protection during transport and storage, observe the following: ● Keep the original packaging for subsequent transportation. ● Devices/replacement parts should be returned in their original packaging.
Introduction 1.
2 Safety notes 2.1 Preconditions for use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device. Always keep the information and symbols in a completely legible state.
Safety notes 2.1 Preconditions for use 2.1.3 FCC Conformity US Installations only: Federal Communications Commission (FCC) rules Note ● This device has been tested and found to comply with the limits Class B digital device part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. ● This device has also been tested and found to comply with the limits §15.
Safety notes 2.2 Laws and directives Note ● This device has been tested and found to comply with the limits RS- 211 - Level Probing Radar Equipment. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. ● This device is certified to measure levels in fixed or mobile enclosed tanks made from metal, concrete or materials with similar RF attenuating properties.
Safety notes 2.3 Requirements for special applications 2.2.
Safety notes 2.4 Use in hazardous areas 2.4 Use in hazardous areas Qualified personnel for hazardous area applications Persons who install, connect, commission, operate, and service the device in a hazardous area must have the following specific qualifications: ● They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures, aggressive, and hazardous media.
Safety notes 2.
Description 3.1 3 Overview SITRANS LR260 SITRANS LR260 is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of solids and liquids in storage vessels including extreme levels of dust and high temperatures, to a range of 30 m (98.4 ft). 3.2 Features The instrument consists of an electronic component coupled to a permanently attached horn antenna with an optional integral Easy Aimer and flange or threaded connection for quick and easy positioning.
Description 3.5 HART communication ● Coal ● Solids and liquids bulk storage vessels 3.4 System configuration Typical PLC/mA configuration with HART 5 ˖ ① ② ③ ④ ⑤ SITRANS LR260 Power supply 1) Active PLC HART modem HART communicator 1) Depending on the system design, the power supply may be separate from the PLC, or integral to it. Loop resistance (total of cable resistance plus 250 Ohm [resistor]) must be less than 550 Ohm for the device to function properly. 2) 3.
Installing/mounting 4.1 4 Basic safety notes DANGER Pressure applications Danger to personnel, system and environment will result from improper disassembly. ● Never attempt to loosen, remove, or disassemble process connection while vessel contents are under pressure. Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components.
Installing/mounting 4.1 Basic safety notes 4.1.1 External stresses and loads CAUTION External stresses and loads Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be released. ● Prevent severe external stresses and loads from acting on the device. 4.1.2 Installation location requirements NOTICE Aggressive atmospheres Damage to device through penetration of aggressive vapors. ● Ensure that the device is suitable for the application.
Installing/mounting 4.2 Disassembly 4.1.3 Proper mounting NOTICE Incorrect mounting The device can be damaged, destroyed, or its functionality impaired through improper mounting. ● Before installing ensure there is no visible damage to the device. ● Make sure that process connectors are clean, and suitable gaskets and glands are used. ● Mount the device using suitable tools. Refer to the information in Technical data (Page 125). Note ● Correct location is key to a successful application.
Installing/mounting 4.3 Proper mounting 4.3 Proper mounting 4.3.1 Nozzle location note Note Beam angle depends on horn size. For details on avoiding false echoes, see Auto False Echo Suppression (Page 55). 4.3.2 Nozzle location ① ② Minimum 1 m (39") Beam angle 2" horn = 15° 3" horn = 10° 4" horn = 8° ● Keep emission cone free of interference from ladders, pipes, I-beams or filling streams. ● Avoid central locations on tall, narrow vessels.
Installing/mounting 4.3 Proper mounting ● Provide easy access for viewing the display and programming via the hand programmer. ● Provide an environment suitable to the housing rating and materials of construction. ● Provide a sunshield if the instrument will be mounted in direct sunlight.
Installing/mounting 4.3 Proper mounting ① ② ③ 4.3.4 Polarization axis Polarization reference point Display Stainless steel Easy Aimer Note When the Easy Aimer ball is loosened, the device is free to tilt to a maximum of 30°.
Installing/mounting 4.3 Proper mounting PP PP r 0D[ ① ② ③ ④ ⑤ Easy Aimer ball locking bolts Top clamping plate (upper socket) Bottom clamping plate (lower socket) Customer gasket as required [recommended thickness 1.5 to 1.8 mm (0.06 to 0.07")] Customer mounting plate, as required ø 102 mm (4") min., central opening Directing the Easy Aimer 1. Holding the electronics enclosure firmly, loosen the Easy Aimer ball locking bolts and gently reposition the enclosure. 2.
Installing/mounting 4.
Installing/mounting 4.3 Proper mounting 4.3.5 Aluminum aimer flanges r r 3" (80 mm) aimer can be adjusted from 0 to 5 degrees 4" (100 mm) aimer can be adjusted from 0 to 10 degrees 6" (150 mm) aimer can be adjusted from 0 to 10 degrees 4.3.6 Air purging system (optional) Note Air purge system is only available with stainless steel horn versions. For more frequent cleaning, a purging system can be installed between the flange and the horn antenna.
Installing/mounting 4.3 Proper mounting This option is only available with the universal flange for purging. Note The Air Purge feature should not be activated with a dust cap in place. • Purge duration, pressure, and interval, will vary with each application. It is the user’s responsibility to determine the requirements depending on the application and cleaning required. • Short duration bursts of high pressure provide more effective cleaning than continuous low pressure air.
Installing/mounting 4.3 Proper mounting ① Purged process connection with factory installed 1/8" NPT plug 1) SCFM (standard cubic feet/minute) referenced to 14.7 psi, +68 °F and 36% relative humidity (RH). 4.3.7 2) Air pressure in vessel can affect purge operation. 3) Not for pressure applications.
Installing/mounting 4.3 Proper mounting The dust cap fits onto the end of the horn and prevents the buildup of dust and other process material inside the horn. ● It is particularly useful for applications in areas of high humidity, or with bulk solids with a high moisture content. ● Three sizes are available, to fit the standard 2", 3" and 4" horns. Installation 1. Thoroughly clean inside the horn. If you remove the horn for easier cleaning, take care not to damage or bend the plastic emitter. 2.
Installing/mounting 4.3 Proper mounting 4.3.9 Aluminum horn with polypropylene lens (dust cover) antenna version The polypropylene lens acting as a dust cover fits onto the end of the horn and prevents the buildup of dust and other process material inside the horn. It is particularly useful for applications in areas of high humidity, or with bulk solids with a high moisture content.
Installing/mounting 4.3 Proper mounting 8. Assemble the aimer adaptor⑥ and the lens assembly④ on to the horn assembly① using 8xM5 screws② (provided in the kit). It is recommended to torque the threads to 25 in lb. 9. Thread the assembly on top of the aimer flange⑦. Ensure the face sealing o-ring⑤ on the on top of the aimer flange⑦ is properly placed. Make sure that intimate contact of the two metallic surfaces of the assembly is obtained. 10.
5 Connecting 5.1 Basic safety notes 5.1.1 Missing PE/ground connection WARNING Missing PE/ground connection Risk of electric shock. Depending on the device version, connect the power supply as follows: ● Power plug: Ensure that the used socket has a PE/ground conductor connection. Check that the PE/ground conductor connection of the socket and power plug match each other. ● Connecting terminals: Connect the terminals according to the terminal connection diagram. First connect the PE/ground conductor.
Connecting 5.2 Connecting SITRANS LR260 5.1.2 Connecting device in energized state in hazardous areas WARNING Connecting device in energized state Risk of explosion in hazardous areas. ● Connect devices in hazardous areas only in a de-energized state. Exceptions: ● Devices having the type of protection "Intrinsic safety Ex i" may also be connected in energized state in hazardous areas. 5.1.
Connecting 5.2 Connecting SITRANS LR260 WARNING Loss of protection Loss of approvals can result from improper connection. ● Check the nameplate on your device, to verify the approval rating. ● Use appropriate cable entry seals to maintain IP or NEMA rating. ● See Instructions specific to hazardous area installation (Page 41). Note Use twisted pair cable: AWG 22 to 14 (0.34 mm2 to 2.5 mm2).
Connecting 5.3 Hazardous area installation Typical PLC/mA configuration with HART 5 ˖ ① ② ③ ④ ⑤ SITRANS LR260 Power supply 1) Active PLC HART modem HART communicator Depending on the system design, the power supply may be separate from the PLC, or integral to it. 1) Loop resistance (total of cable resistance plus 250 Ohm [resistor]) must be less than 550 Ohm for the device to function properly. 2) 5.
Connecting 5.3 Hazardous area installation 5.3.1 Instructions specific to hazardous area installation Device nameplate (ATEX/IECEX/INMETRO/C-TICK) SITRANS LR260 7MLxxxx-xxxxx-xxxx Serial No: GYZ / B1034567 Encl.: NEMA / TYPE 4X, 6, IP67, IP68 Amb.Temp.: – 40°C to 80°C Power Rating: 24V Nom., 30 V KCC-REM-S49 SITRANSLR Max.
Connecting 5.3 Hazardous area installation A5E03745453 - Non-incendive wiring (US/Canada only) FM/CSA Class 1, Div 2 connection drawing number A5E03745541 can be downloaded from the product page of our website at: ● www.siemens.com/LR260. ● Go to Technical Info > Images, graphics, drawings. ● For power demands see Startup Behavior (Page 162). ① The ATEX certificate listed on the nameplate. The ATEX certificate listed on the nameplate can be downloaded from the product page of our website at: www.
Connecting 5.3 Hazardous area installation ● When these products are used in the presence of combustible dust, any glands, conduit entry devices or blanking elements fitted to the equipment shall be suitable for use in the presence of combustible dusts and certified as such by a notified body; the installation of these devices shall not compromise the IP6X rating of the equipment enclosure. ● Unused cable entries shall be fitted with blanking elements that can only be removed with the aid of a tool.
Connecting 5.3 Hazardous area installation 9. The certificate numbers have an ‘X’ suffix, which indicates that special conditions for safe use apply. Those installing or inspecting this equipment must have access to the certificates. 10.If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection is not compromised.
Commissioning 6.1 Basic safety notes 6.1.1 Hot surfaces 6 WARNING Hot surfaces Risk of burns resulting from hot surfaces. ● Take corresponding protective measures, for example by wearing protective gloves. 6.1.2 Toxic gases and liquids DANGER Toxic gases and liquids Danger of poisoning when venting the device: if toxic process media are measured, toxic gases and liquids can be released.
Commissioning 6.2 Local commissioning 6.2 Local commissioning The handheld programmer used with this device contains lithium batteries that are nonreplaceable. Lithium batteries are primary power sources with high energy content designed to provide the highest possible degree of safety. WARNING Potential hazard Lithium batteries may present a potential hazard if they are abused electrically or mechanically.
Commissioning 6.2 Local commissioning 6.2.2.2 Remote Quick Start options ● locally [see Quick Start Wizard via the handheld programmer (Page 51)] ● or from a remote location [see Quick Start Wizard via SIMATIC PDM (Page 60), or Quick Start Wizard via AMS Device Manager] For more complex setups see Application Examples (Page 147), and for the complete range of parameters see Parameter Reference (Page 73). 6.2.2.
Commissioning 6.2 Local commissioning 6.2.2.4 The LCD display Measurement mode display Normal operation 1 2 3 4 [M] LEVEL 18.91 21.40 rC DATA EXCH.
Commissioning 6.2 Local commissioning PROGRAM mode display Navigation view 2.2.1 INPUT SENSOR CALIB. ECHO PROC. TVT SETUP TVT SHAPER ① ② ③ Menu bar Current menu ④ ⑤ Current item number Pointer Current item ● A visible menu bar indicates the menu list is too long to display all items. ● A band halfway down the menu bar indicates the current item is halfway down the list.
Commissioning 6.2 Local commissioning 6.2.2.5 Handheld programmer (Part No. 7ML1930-1BK) The programmer is ordered separately. 6.2.2.6 Key functions in measurement mode Key functions in measurement mode Key Function Result Updates the loop current New value is displayed in LCD secondary re‐ gion. Updates internal enclosure temperature reading Updates echo confidence value New value is displayed in LCD secondary re‐ gion.
Commissioning 6.2 Local commissioning 6.2.3 Programming 6.2.3.1 Programming the radar device Note ● While the device is in PROGRAM mode the output remains fixed and does not respond to changes in the device. ● The device automatically returns to Measurement mode after a period of inactivity in PROGRAM mode (between 15 seconds and 2 minutes, depending on the menu level). 6.2.3.
Commissioning 6.2 Local commissioning 6.2.3.3 Application Type (1.1.) Options STEEL Silo construction CONCRETE Default: STEEL 6.2.3.4 Response Rate (1.2.) Sets the reaction speed of the device to measurement changes in the target range. Options SLOW 0.1 m/minute MED 1.0 m/minute FAST 10.0m/minute Default: FAST Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Slower settings provide higher accuracy; faster settings allow for more level fluctuation.
Commissioning 6.2 Local commissioning Operation Types ① ② ③ ④ ⑤ ⑥ 6.2.3.7 Sensor reference point (flange face) High calibration point Distance Space Level Low calibration point Low Calibration Point (LOW CALIB. PT.) (1.5.) Distance from Sensor Reference to Low Calibration Point: usually process empty level. (See Operation (Page 52) types for an illustration.) Range: 0.0000 to 30.
Commissioning 6.2 Local commissioning 6.2.3.8 High Calibration Point (HIGH CALIB. PT.) (1.6.) Distance from Sensor Reference to High Calibration Point: usually process full level. (See Operation (Page 52) types for an illustration.) Values Range: 0.0000 to 30.000 m Default: 0.0 m Related parameters Near Range (2.2.1.12.) (Page 81) When setting the High Calibration Point value, note that echoes are ignored within Near Range (2.2.1.12.) (Page 81) 6.2.3.9 Apply (1.7.
Commissioning 6.2 Local commissioning 1 2 6.2.3.11 ① Transmit icon, de‐ selected ② Exit icon, selected a. In PROGRAM mode, navigate to: LEVEL METER> DIAGNOSTICS> ECHO PROFILES (3.1) b. Press RIGHT arrow c. In the Profile screen, press UP arrow update the profile. d. Press DOWN arrow to request a profile. to select the Transmit icon, and Right arrow to select the Exit icon, then Right arrow to to return to previous menu. Device address The default address for the device is 0.
Commissioning 6.3 Application examples 6.3 Application examples 6.3.1 Application examples Note In the applications illustrated below, values are for example purposes only. You can use these examples as setup references. Enter the values in the parameter tables to select the corresponding functions. Configure the basic settings using the Quick Start wizard parameters. (These parameters are inter-related, and changes take effect only after you select FINISH to apply changes in the final step.
Commissioning 6.3 Application examples P P ① ② ③ ④ ⑤ Low calibration point Level High calibration point Sensor reference point SITRANS LR260 Fill rate = 0.09 m/minute (Low Cal Pt. minus High Cal Pt.) / fastest fill/empty time = (16 m – 0.5 m) / 180 min. = 15.5 m /180 min. = 0.09 m/min. Quick start setting Description APPLICATION (Page 74) STEEL RESPONSE RATE (Page 74) SLOW UNITS (Page 75) m OPERATION (Page 75) LEVEL Material level referenced from Low Calibration Point.
Commissioning 6.
7 Operating 7.1 Operating via SIMATIC PDM SIMATIC PDM is a software package used to commission and maintain process devices. Please consult the operating instructions or online help for details on using SIMATIC PDM. You can find more information on versions and compatibility at our website. 7.1.1 Functions in SIMATIC PDM The graphic interface in the device makes monitoring and adjustments easy. 7.1.1.
Operating 7.1 Operating via SIMATIC PDM 7.1.1.3 Initial setup Initial setup It is required to obtain the SITRANS LR260 EDD from the product support website and install into PDM using the device integration manager utility. 7.1.1.4 Updating the Electronic Device Description (EDD) You can locate the EDD in Device Catalog, under Sensors/Level/Echo/SiemensMilltronics/ SITRANS LR260. The EDD revision must match the Firmware revision in the device. To install a new EDD: 1.
Operating 7.1 Operating via SIMATIC PDM Please consult the operating instructions or online help for details on using SIMATIC PDM. 7.1.2.2 Quick start note Quick start Note ● A reset to Factory Defaults should be performed before running the Quick Start Wizard if device has been used in a previous application. See Master Reset via SIMATIC PDM (Page 103).
Operating 7.1 Operating via SIMATIC PDM 7.1.2.4 Quick start steps with images Step 1 – Identification Note ● The layout of the dialog boxes shown may vary according to the resolution setting for your computer monitor. ● SITRANS PDM limits the TAG field to a maximum of 24 characters. 1. Click on Read Data from Device to upload Quick Start parameter settings from the device to the PC/PG and ensure PDM is synchronized with the device. 2. If required, change the language for the local user interface. 3.
Operating 7.1 Operating via SIMATIC PDM Step 3 – Ranges Set the parameters, and click on NEXT. Step 4 – Summary Check parameter settings, and click on BACK to return and revise values, FINISH to save settings offline, or FINISH AND DOWNLOAD to save settings offline and transfer them to the device. The message Quick Start was successful will appear. Click on OK.
Operating 7.1 Operating via SIMATIC PDM 7.1.3 Changing parameter settings using SIMATIC PDM Note ● For a complete list of parameters, see Parameter Reference (Page 73). ● Clicking on Cancel during an upload from device to SIMATIC PDM will result in some parameters being updated. Many parameters are accessed via pull-down menus in PDM. See Parameters accessed via pull-down menus (Page 65) for others. 1. Launch SIMATIC PDM, connect to device, and upload data from device. 2.
Operating 7.1 Operating via SIMATIC PDM 7.1.5 Parameters accessed via pull-down menus 7.1.5.1 Parameters accessed via pull-down menus Click on Device or View to open the associated pull-down menus. 1 ① 7.1.5.2 pull-down menus Display To compare outputs in real time, open the menu View – Display. 7.1.5.3 Echo profile Open the menu View - Echo Profile.
Operating 7.1 Operating via SIMATIC PDM Note ● Double click on each axis and record the Xscale and Data Scale values, so that you can restore the default view by resetting to these values. ● You can save a profile or delete a saved profile. ● After saving a profile, open menu View – Echo profile. 7.1.5.4 Trend Note Double click on each axis and record the Xscale and Data Scale values, so that you can restore the default view by resetting to these values. Open the menu View – Trend. 7.1.5.
Operating 7.1 Operating via SIMATIC PDM SITRANS LR260 first learns the echo profile. Then the learned profile, or part of it, is used to screen out false echoes. (See Auto False Echo Suppression (Page 87)for a more detailed explanation.) 1. Determine Auto Suppression Range (the distance within which the learned TVT will replace the default TVT).
Operating 7.1 Operating via SIMATIC PDM ● Press Measure to refresh the echo profile and load the current TVT curve from the device. ● Change the position of the cursor on the TVT curve using the Point+ and Point– buttons: raise and lower the curve using Offset+ and Offset– (entered in dB). ● Alternatively, enter values for Point and Offset directly into the dialog boxes. ● If desired, click on the TVT breakpoints tabs to see settings. ● Click on Transfer to Device. 7.1.5.
Operating 7.1 Operating via SIMATIC PDM 7.1.5.9 Maintenance You can set schedules and reminders for: ● device maintenance based on its projected lifetime ● sensor maintenance based on its projected lifetime ● service ● calibration To set Device/Sensor Maintenance schedules: 1. Open the menu Device - Maintenance, and click on the Remaining Device/Sensor Lifetime tab. 2. Modify desired values, and click on Write. 3. Click on Read, to see the effects of your modification. 4.
Operating 7.1 Operating via SIMATIC PDM Use Device Reset to reset all user parameters excluding device addresses, the parameter block Identification, and Maintenance Schedule parameters to the default settings. 1. Open the menu Device - Device Reset and click on OK to perform a reset to Factory Defaults. 2. After the reset is complete, upload parameters to the PC/PG. Note If you are performing a reset after replacing the device with a different instrument, do not upload parameters to the PC/PG. 7.1.5.
Operating 7.1 Operating via SIMATIC PDM To simulate a user-defined mA value: 1. Open the menu Device - Simulate AO. 2. Select Other, enter the simulated value, and click on OK. The message 'Field Device fixed at new value' appears. Click on OK. 3. When you are ready to end simulation, select End and click on OK to return the device to the original output level. 7.1.5.15 HART Communication Sets the number of request/response preambles (default 5).
Operating 7.
8 Parameter reference 8.1 Parameter reference Note ● Parameter names and menu structure are almost identical for SIMATIC PDM and the local user interface (LUI). ● Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. ● Mode toggles between PROGRAM and Measurement Modes. ● For Quick Access to parameters via the handheld programmer, press Home , then enter the menu number, for example: 2.2.1.
Parameter reference 8.4 Quick start (1.) Device menus View menus Quick Start (Page 74) Auto False Echo Suppression (Page 87) TVT shaper (Page 67) Update Maintenance (Page 69) Device Reset (Page 69) Simulate AO (Page 70) Write Locking 8.3 Quick Start Wizard The Quick Start wizard groups together all the settings you need to configure for a simple application. You can access it either via SIMATIC PDM, or via the handheld programmer.
Parameter reference 8.4 Quick start (1.) 8.4.3 Units (1.3.) Select the units for the Quick Start variables (high and low calibration point, and level, distance, or space). Options M, CM, MM, FT, IN Default: M 8.4.4 Operation (1.4.) Options NO SERVICE Stops updating measurements and associated loop current. Last valid measurement value is displayed. LEVEL Distance to material surface ref‐ erenced from Low Calibration Point (process empty level).
Parameter reference 8.4 Quick start (1.) Operation Types ① ② ③ ④ ⑤ ⑥ 8.4.5 Sensor reference point (flange face) High calibration point Distance Space Level Low calibration point Low Calibration Point (LOW CALIB. PT.) (1.5.) Distance from Sensor Reference to Low Calibration Point: usually process empty level. (See Operation (Page 75) types for an illustration.) Range: 0.0000 to 30.
Parameter reference 8.5 Setup (2.) 8.4.6 High Calibration Point (HIGH CALIB. PT.) (1.6.) Distance from Sensor Reference to High Calibration Point: usually process full level. (See Operation (Page 75) types for an illustration.) Values Range: 0.0000 to 30.000 m Default: 0.0 m Related parameters Near Range (2.2.1.12.) (Page 81) When setting the High Calibration Point value, note that echoes are ignored within Near Range (2.2.1.12.) (Page 81) 8.4.7 Apply (1.7.
Parameter reference 8.5 Setup (2.) 8.5.3 Loader Revision (LOADER REV.) (2.1.2.) Corresponds to the software used to update the SITRANS LR260. Read only. 8.5.4 Hardware Revision (HARDWARE REV.) (2.1.3.) Corresponds to the electronics hardware of the SITRANS LR260. Read only. 8.5.5 Input (2.2.) 8.5.6 Sensor Calibration (SENSOR CALIB.) (2.2.1.) You can configure each of the related parameters, to suit your particular application. 8.5.7 Antenna (2.2.1.1.) Sets antenna type.
Parameter reference 8.5 Setup (2.) 8.5.9 Operation (2.2.1.5.) NO SITRANS LR260 stops updating measurements and SERVICE associated loop current. Last valid measurement value is displayed. Options * LEVEL Distance to material surface referenced from Low Cali‐ bration Point (process empty level). SPACE Distance to material surface referenced from High Cali‐ bration Point (process full level). DIS‐ TANCE Distance to material surface referenced from Sensor Reference Point.
Parameter reference 8.5 Setup (2.) 8.5.10 Low Calibration Pt. (LOW CALIB. PT.) (2.2.1.6.) Distance from Sensor Reference to Low Calibration Point (corresponding to Low Level Point). Units are defined in Sensor Units. ① ② ③ ④ 1) sensor reference point (flange face) high calibration point Level1 low calibration point The point from which level measurement is referenced. See Dimensions. (Page 131) Values Range: 0 to 30 m. Default dependent on horn type 8.5.
Parameter reference 8.5 Setup (2.) When setting the High Calibration Point value, note that echoes are ignored within Near Range (2.2.1.11). 8.5.12 Limit Sensor Value (2.2.1.8.) When On, limits the sensor value to the range between Low Calibration Point and High Calibration Point. Options 8.5.13 ON, OFF. Default: On Near Range (2.2.1.12.) The range in front of the device (measured from the sensor reference point) within which any echoes will be ignored, defined in sensor units.
Parameter reference 8.5 Setup (2.) 8.5.15 Sensor Offset (2.2.1.25.) A constant offset that can be added to Sensor value1) to compensate if the sensor has been changed. Units are defined in Sensor Units. Values Range: -99 999 to 99 999 Default: 0 m The value produced by the echo processing which represents the distance from the sensor reference point to the target. 1) 8.5.16 Echo processing (ECHO PROC.)(2.2.4.) 8.5.16.1 Echo select (2.2.4.1.) Algorithm (2.2.4.1.1.
Parameter reference 8.5 Setup (2.) Note Rising Edge is recommended for solids. COM is recommended for flat targets and liquids. Echo Threshold (2.2.4.1.3.) Sets the minimum echo confidence that the echo must meet in order to prevent a Loss of Echo condition and the expiration of the LOE timer. When Echo Confidence exceeds the Echo Threshold, the echo is accepted as a valid echo and is evaluated. Values Range: 0 to 99 dB Default: 5 Related Parameters 2.4.1.
Parameter reference 8.5 Setup (2.) 8.5.16.4 Up Sampling (2.2.4.2.4.) Specifies the number of consecutive echoes that must appear above the echo currently selected, before the measurement is accepted as valid. Values Range: 1 to 50 Default: 5 8.5.16.5 Down Sampling (2.2.4.2.5.) Specifies the number of consecutive echoes that must appear below the echo currently selected, before the measurement is accepted as valid. Values Range: 1 to 50 Default: 5 8.5.16.6 Window (2.2.4.2.6.
Parameter reference 8.5 Setup (2.) 8.5.16.7 Filtering (2.2.4.3.) Damping Filter (2.2.4.3.2.) The time constant for the damping filter. The damping filter smooths out the response to a sudden change in level. This is an exponential filter and the engineering unit is always in seconds. See Damping (Page 156) for more detail. Values Range: 0 to 1000 s Default: 0 s Narrow Echo Filter (2.2.4.3.6.) Filters out echoes of a specific width.
Parameter reference 8.5 Setup (2.) 8.5.16.8 Noise (2.2.4.5.) Echo Confidence (2.2.4.5.1.) Indicates echo reliability. It displays the echo confidence of the last measurement. Echo Threshold defines the Echo Confidence minimum criterion for echo confidence. Echo confidence must be greater than Echo Threshold to be accepted as valid and evaluated for an echo. Values (view only) 0 to 99 dB ---- Related Parameters Shot not used 2.2.4.1.3. Echo Threshold In PDM, open the menu View – Echo Profile. 2.2.4.
Parameter reference 8.5 Setup (2.) 8.5.19 Auto False Echo Suppression (2.2.5.2.) Enables a ’learned’ TVT curve to be used in place of the default TVT curve. See Auto False Echo Suppression (Page 153). Note ● If possible adjust Auto False Echo Suppression parameters with an empty or almost empty vessel. ● Set Auto False Echo Suppression and Auto False Echo Range during startup, if possible. Options * OFF Default TVT curve will be used. ON ’Learned’ TVT curve will be used.
Parameter reference 8.5 Setup (2.) 8.5.21 Shaper Mode (2.2.5.4.) Adjusts the TVT curve at a specified range. Options ON * 8.5.22 OFF TVT Type (2.2.5.6.) Selects the TVT shaping type to be applied to the echo profile to extract the true echo. Short Curved Short Flat Long Flat Long Smooth Front Long Smooth Options Slopes * Long Smooth 2 Short Curved 2 8.5.23 TVT shaper (2.2.6.) A breakpoint on the TVT curve. This allows you to reshape the TVT curve to avoid unwanted echoes.
Parameter reference 8.5 Setup (2.) 8.5.26 Shaper 19-27 (2.2.6.3.) Values Range: –50 to 50 dB Default: 0 dB 8.5.27 Shaper 28-36 (2.2.6.4.) Values Range: –50 to 50 dB Default: 0 dB 8.5.28 Shaper 37-40 (2.2.6.5.) Values Range: –50 to 50 dB Default: 0 dB 8.5.29 Rate (2.2.7.) 8.5.30 Response Rate (2.2.7.1.) Note Changing Response Rate resets Fill Rate, Empty Rate, Damping Filter and Echo Lock. Sets the reaction speed of the device to measurement changes.
Parameter reference 8.5 Setup (2.) 8.5.31 Fill Rate (FILL RATE/MIN.) (2.2.7.2.) Defines the maximum rate at which the reported sensor value is allowed to increase. Allows you to adjust the SITRANS LR260 response to increases in the actual material level. Fill Rate is automatically updated whenever Response Rate is altered. Values Range: 0 to 30 m / min. Default: 10 m/min.
Parameter reference 8.5 Setup (2.) 8.5.35 Space Measurement (SPACE MEAS.) (2.2.8.3.) The value for space. Read Only. In SIMATIC PDM, open the menu View – Display, and select the tab Display. 8.5.36 Distance Measurement (DISTANCE MEAS.) The value for distance. Read Only. In SIMATIC PDM, open the menu View – Display, and select the tab Display. 8.5.37 Output (2.3.) 8.5.37.1 mA Output (2.3.1.) 8.5.38 mA Output (2.3.1.) 8.5.39 mA Output Value (2.3.1.1.) The loop current value in mA.
Parameter reference 8.5 Setup (2.) Note ● The mA Output Function is set independently from the setting in Operation. Set Operation first and then mA Output Function. (Operation resets mA Output Function to the same value.) ● The mA Output Function controls the primary value and the loop current for the SITRANS LR260. Use caution when changing the mA Output function when connected to a HART network. ● mA Output Function must be set to Manual before you can modify the mA Output Value (2.3.1.1).
Parameter reference 8.5 Setup (2.) Enter the reading that is to correspond to a 4 mA output. Units are defined in Sensor units for Level, Space, or Distance.1) 4 mA setpoint can be set less than 0 m, and 20 mA setpoint can be set greater than 30 m when using handheld programmer. Recommended range is 0 to 30 m. 1) 8.5.42 20 mA Setpoint (2.3.1.4.) Sets the process level corresponding to the 20 mA value.
Parameter reference 8.5 Setup (2.) 8.5.45 4 mA Output Trim (2.3.1.7.) Calibrates the 4 mA output. The mA output of the device is pre-calibrated; however, 4 mA Output Trim can be used to trim remote displays or inputs. Values Range: 2.0 to 6.0 (mA) Related parameters 20 mA Output Trim 1. Set mA Output Function to Manual. 2. Set mA Output Value to 4 mA. 3. Attach a calibrated meter and check the output at the terminals; record the remote reading in mA. 4. Enter this value in 4 mA Output Trim. 5.
Parameter reference 8.6 Diagnostics (3.) Note The last valid reading is maintained until the Fail-safe timer expires. After the timer expires, the reading is set based on Fail-safe Material Level. 8.5.49 Fail-safe Material Level (FAILSAFE MAT. LE) (2.4.2.) HI: Use 22.6 mA (max. mA Limit) as material level LO: Use 3.6 mA (min. mA Limit) as material level Options * HOLD: Level remains at last reading VALUE: User-selected value (defined in Fail-safe Level) 8.5.50 Fail-safe Level (2.4.4.
Parameter reference 8.6 Diagnostics (3.) To request a profile via the handheld programmer: ① ② ③ ④ Echo confidence value Algorithm selection (true first) Distance value ⑤ ⑥ TVT curve ⑦ Material level Exit icon, selected Transmit icon, deselected 1. In PROGRAM mode, navigate to LEVEL METER > DIAGNOSTICS > ECHO PROFILE (3.1) 2. Press RIGHT arrow to request a profile. 3. In the Profile screen, press UP arrow to select the Transmit icon, and Right ARROW to update the profile. 4.
Parameter reference 8.6 Diagnostics (3.) 8.6.6 Remaining Device Lifetime (REMAIN. DEV. LIFE.) (3.15.) Note ● Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up Maintenance/Service schedules, based on operating hours instead of a calendar-based schedule. See also Remaining Sensor Lifetime (Page 98), Service Interval (Page 105), and Calibration Interval (Page 108).
Parameter reference 8.6 Diagnostics (3.) 8.6.8 Remaining Device Lifetime (REMAIN. LIFETIME) (3.15.2.) Read only. Remaining Lifetime in selected units. 8.6.9 Maintenance Required Limit (MAINT. REQ. LIMIT) (3.15.3.) If the Remaining Lifetime is equal to or less than this limit, the device sets Maintenance Required. Values Range: 0 to 20 years Default: 0.164 years In SIMATIC PDM, open the menu Device – Maintenance, click on Remaining Device Lifetime. 1. Modify limit values as required. 2. Enable 3.15.5.
Parameter reference 8.6 Diagnostics (3.) First set the limit values in Maintenance Required Limit (3.15.3.)/ Maintenance Demanded Limit (3.15.4.). Select the desired Maintenance Alert Activation option. 8.6.12 Total Expected Device Life (TOTAL EXP. LIFE) (3.15.6.) Note The device always operates in years. Changing the units affects only the parameter view of the Remaining Device Lifetime parameters in SIMATIC PDM. Allows you to override the factory default.
Parameter reference 8.6 Diagnostics (3.) To acknowledge an alert via the handheld programmer: 1. Press RIGHT arrow twice to open parameter view and activate Edit Mode. 2. Press RIGHT arrow to acknowledge the alert. 8.6.16 Remaining Sensor Lifetime (REMAIN SENS. LIFE.) (3.16.) Note Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up Maintenance/Service schedules, based on operating hours instead of a calendar-based schedule.
Parameter reference 8.6 Diagnostics (3.) 8.6.17 Total Sensor Operating Time (SENS OP. TIME) (3.16.1.) Displays the amount of time the sensor has been operating in selected units. Can be reset to zero after performing a service or replacing the sensor. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Remaining Sensor Lifetime tab, and click on Sensor Replaced to restart the timer and clear any fault messages.
Parameter reference 8.6 Diagnostics (3.) 8.6.21 Maintenance Alert Activation (ALERT ACTIVATION) (3.16.5.) Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device – Maintenance. Allows you to enable a maintenance limit. Warning Limit 1 (Maintenance Required Limit) Warning Limit 2 (Maintenance Demanded Limit) Options Warning Limits 1 and 2 (Maintenance Required and Main‐ tenance Demanded Limits) * OFF 1.
Parameter reference 8.7 Service (4.) To acknowledge an alert via SIMATIC PDM: 1. Open the menu View – Device Status and click on the Maintenance tab. 2. In the Sensor Lifetime section click on Acknowledge Warnings. To acknowledge an alert via the handheld programmer: 1. Press RIGHT arrow twice to open parameter view and activate Edit Mode. 2. Press RIGHT arrow to acknowledge the alert. 8.7 Service (4.) 8.7.1 Device Reset (4.1.
Parameter reference 8.7 Service (4.) Enables a faster rate of measurement from the device by disabling most of the display area. Only the bar graph will be refreshed when LCD Fast Mode is set to ON. When Fast Mode is set to ON, there is a delay of 30 minutes with no pressed buttons before actions result. Values ON or OFF Default: OFF 8.7.4 LCD Contrast (4.4.) The factory setting is for optimum visibility at room temperature and in average light conditions.
Parameter reference 8.7 Service (4.) 8.7.7 Memory Test (MEM. TEST) (4.11.) Allows verification of the RAM, EEPROM, and Flash memory of the SITRANS LR260. LCD Display Handheld programmer entry IDLE No test in progress. BUSY Test in progress. PASS Memory test successful. FAIL Test failed. Err1 Test returned unexpected re‐ sults. P Oxcafe Test passed with result data. F Oxcafe Test failed with result data. 1 to 9 Any numeric key from 1 to 9 ac‐ tivates test.
Parameter reference 8.7 Service (4.) 8.7.9 Time Last Serviced (TIME LAST SERV.) (4.16.1.) Time elapsed since device was last serviced in selected units. Can be reset to zero via the handheld programmer (after performing a service.) To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Service Interval tab, and click on Service Performed to restart the timer and clear any fault messages. ● Via the handheld programmer, manually reset Time Last Serviced to zero. 8.7.
Parameter reference 8.7 Service (4.) Allows you to enable a maintenance limit. * Timer off On - no limits On - limit 1 Values On - limits 1 and 2 On - limit 2 1. First set the limit values in Maintenance Required Limit/Maintenance Demanded Limit. 2. Select the desired Maintenance Alert Activation option 8.7.14 Total Service Interval (4.16.6.) Note The device always operates in years. Changing the units affects only the parameter view of the Service Interval parameters in SIMATIC PDM.
Parameter reference 8.7 Service (4.) To acknowledge an alert via SIMATIC PDM: 1. Open the menu View – Device Status and click on the Maintenance tab. 2. In the Service Schedule Status section click on Acknowledge Warnings. To acknowledge an alert via the handheld programmer: 1. Press RIGHT arrow twice to open parameter view and activate Edit Mode. 2. Press RIGHT arrow to acknowledge the alert. 8.7.18 Calibration Interval (CALIB. INTERVAL) (4.17.
Parameter reference 8.7 Service (4.) 8.7.21 Maintenance Required Limit (MAINT. REQ. LIMIT) (4.17.3.) If Remaining Lifetime is equal to or less than this limit, the device sets Maintenance Required. Values Range: 0 to 20 years Default: 0.164 years 1. Modify limit values as required. 2. Set Maintenance Alert Activation to the desired option. 8.7.22 Maintenance Demanded Limit (MAINT. DEM. LIMIT) (4.17.4.) If Remaining Lifetime is equal to or less than this limit, the device sets Maintenance Demanded.
Parameter reference 8.7 Service (4.) 8.7.24 Total Calibration Interval (TOTAL CALIB. INTRV.) (4.17.6.) Note The device always operates in years. Changing the units affects only the parameter view of the Calibration Interval parameters in SIMATIC PDM. User-configurable recommended time between product calibrations. Units1): hours, days, years Values Range: 0 to 20 years Default: 1 year 1) 8.7.25 Units are selectable only via SIMATIC PDM. Maintenance Status (MAINT. STAT.) (4.17.7.) Read only.
Parameter reference 8.8 Communication (5.) 8.8 Communication (5.) 8.8.1 Device Address (5.1.) Sets the device address or poll ID on a HART network. Any address other than 0 will cause the output current to be a fixed value, and the current will not indicate the reading. Values Range: 0 to 15 Default: 0 To set the address via the handheld programmer: ● Press RIGHT arrow to activate PROGRAM mode and open menu level 1. ● Press DOWN arrow repeatedly to navigate to COMMUNICATION (menu item 5).
Parameter reference 8.9 Security (6.) 8.9 Security (6.) 8.9.1 Lock (6.1.) Note ● Do not lose this number value. ● This lock affects only the handheld programmer. A remote master can change configuration if Communication Control is set to allow this. Prevents any changes to parameters via the handheld programmer. Handheld programmer Values Range: 1 to 9999 * Related parameter 1954 (unlock value) Off (enables local programming) Any other value On (disables local programming) Unlock value (6.2.
Parameter reference 8.10 Language (7.) 8.10 Language (7.) Selects the language to be used on the LCD.
Parameter reference 8.10 Language (7.
Service and maintenance 9.1 Basic safety information 9.1.1 Maintenance 9 The device is generally maintenance-free. However, a periodic inspection according to pertinent directives and regulations must be carried out. An inspection can include check of: ● Ambient conditions ● Seal integrity of the process connections, cable entries, and cover screws ● Reliability of power supply, lightning protection, and grounds 9.1.
Service and maintenance 9.2 Cleaning 9.2 Cleaning 9.2.1 Cleaning the enclosure Cleaning the enclosure ● Clean the outside of the enclosure with the inscriptions and the display window using a cloth moistened with water or a mild detergent. ● Do not use any aggressive cleansing agents or solvents, e.g. acetone. Plastic parts or the painted surface could be damaged. The inscriptions could become unreadable. 9.2.
Service and maintenance 9.4 Return procedure 9.3 Maintenance and repair work 9.3.1 Impermissible repair of the device WARNING Impermissible repair of the device ● Repair must be carried out by Siemens authorized personnel only. 9.3.2 Maintenance The device is maintenance-free. However, a periodic inspection according to pertinent directives and regulations must be carried out.
Service and maintenance 9.5 Disposal Required forms ● Delivery note ● Return goods note (http://www.siemens.com/processinstrumentation/returngoodsnote) with the following information: – Product (item description) – Number of returned devices/replacement parts – Reason for returning the item(s) ● Declaration of decontamination (http://www.siemens.com/sc/ declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues.
10 Diagnosing and troubleshooting 10.1 Communication troubleshooting 1. Check the following: – There is power at the device. – The LCD shows the relevant data. – The device can be programmed using the handheld programmer. – If any fault codes are being displayed see General Fault Codes (Page 121) for a detailed list. 2. Verify that the wiring connections are correct. 3. See the table below for specific symptoms. Symptom Corrective action The device cannot be programmed via the handheld programmer.
Diagnosing and troubleshooting 10.2 Device status icons 10.
Diagnosing and troubleshooting 10.3 General fault codes 10.3 General fault codes Note ● If more than one fault is present, the device status indicator and text for each fault alternate at 2 second intervals. ● Some faults cause the device to go to Fail-safe mode (Fault 52). These are indicated with an asterisk (*). Code/ Icon S: 0 * Meaning Corrective Action The device was unable to get a measurement within the Fail-safe LOE Timer period.
Diagnosing and troubleshooting 10.3 General fault codes Code/ Icon Meaning Corrective Action S: 12 Internal temperature of device has exceeded ● Relocate device and/or lower process temperature specifications: it is operating outside its temper‐ enough to cool device. ature range. ● Inspect for heat-related damage and contact your local Siemens representative if repair is required. ● Fault code will persist until a manual reset is performed using SIMATIC PDM or the LCD interface.
Diagnosing and troubleshooting 10.4 Operation troubleshooting Code/ Icon Meaning Corrective Action Repair required: contact your local Siemens representative. S: 45 * No valid boot program detected: firmware cor‐ rupt S: 48 * User configuration is invalid. One or more of pa‐ ● Reconfigure the unit.
Diagnosing and troubleshooting 10.4 Operation troubleshooting Symptom Cause Action Display shows location or aiming: ● check to ensure nozzle is vertical ● poor installation ● flange not level ● use Auto False Echo Suppression (2.2.5.2 (Page 87)) and check Auto Suppression Range (2.2.5.3) (Page 87) to ensure nozzle protrudes from end of vessel nozzle. antenna malfunction: ● check Current Internal Temperature (3.14.
11 Technical data Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. 11.1 Power General Purpose Intrinsically Safe Non-Sparking Non-incendive (FM/CSA US/Canada only) Nominal 24 V DC at 550 Ohm ● Maximum 30 V DC ● 4 to 20 mA ● Max. startup current see Startup Behaviour (Page 162). 11.
Technical data 11.3 Interface Min. detectable dis‐ tance2) Stainless steel 0.05 m (1.97") from end of horn Aluminum horn, 0.2 m (7.90") from end of horn with polypropy‐ lene lens antenna Update time3) minimum 2 seconds, depending on settings for Response Rate (2.2.7.1.) (Page 89) and LCD Fast Mode (4.3.) (Page 103) Influence of ambient temperature < 0.003%/K (average over full temperature range, refer‐ enced to maximum range) Dielectric constant of material measured Minimum dK Memory 1.
Technical data 11.5 Environmental 11.4 Process connec‐ tion: Mechanical Stainless steel Flange and horn 304 stainless steel or aluminum and polypropylene Universal aimer flanges 1) 50 mm (2"), 80 mm (3"), 100 mm (4"), 150 mm (6") Horn 50 mm (2"), 80 mm (3"), 100 mm (4") Air Purge Connec‐ tion: equipped with female 1/8" NPT fit‐ ting Weight: Standard model < 8.14 kg (17.
Technical data 11.6 Process Location indoor/ outdoor Altitude 5000 m (16,404 ft) max. Ambient temperature Storage −40 to +80 °C (−40 to +176 °F) Operating −40 to +80 °C (−40 to +176 °F) Relative humidity suitable for outdoor Type 4X, Type 6, IP67, IP68 enclosure (see note above) Installation category I Pollution degree 4 11.
Technical data 11.8 Programmer data - 7ML1930-1BK 11.7 Approvals data Application type Non-hazardous Hazardous LR260 version Approval rating General purpose C CSAUS, FM, CE, RCM Radio Europe (RED), FCC, Industry Canada Intrinsically safe (Page 41) ATEX II 1G Ex ia IIC T4 Ga Valid for: N. America, Eu‐ rope Europe ATEX II 1D, 1/2D, 2D Ex ta IIIC 100°C Da ATEX II 3G Ex nA II T4 Gc IECEx SIR 11.0153X Ex ia IIC T4 Ga, Ex ta IIIC T100 °C Da International IECEx SIR 07.
Technical data 11.
Dimension drawings 12.1 12 Stainless steel aimer version Note ● Process temperature and pressure capabilities are dependent upon information on the process device tag. ● Signal amplitude increases with horn diameter, so use the largest practical size.
Dimension drawings 12.1 Stainless steel aimer version ① ② ③ ④ ⑤ 132 Height to sensor reference pointa) Sensor reference point ½" NPT or M20 cable entry Threaded cover Enclosure/electronics ⑥ Process device tag ⑦ ⑧ ⑨ ⑩ Universal slotted flange Optional horn extension Horn antenna Antenna O.D.
Dimension drawings 12.2 Stainless steel threaded version Dimensions in mm (inch) Antenna type Height to sen‐ sor reference pointa) Optional horn ex‐ tension Measurement range 2 inch horn: 163 mm (6.4") 49.0 mm (1.90") 168 mm (6.40") 100 mm (4.0") 20m (65.6 ft) 3 inch horn: 228 mm (9.0") 74.5 mm (2.90") 228 mm (9.00") 4 inch horn: 285 mm (11.2") 97.5 mm (3.80") 285 mm (11.20") a) 12.2 Antenna O.D. 200 mm (8.0") 500 mm (19.7") 1000 mm (39.4") 30m (98.4 ft) 30m (98.
Dimension drawings 12.2 Stainless steel threaded version ① ② ③ ④ ⑤ 134 Height to sensor reference point ½" NPT or M20 cable entry Threaded cover Enclosure/ electronics Retaining collar ⑥ ⑦ ⑧ ⑨ ⑩ Process connection tag Sensor reference point Optional 100 mm (4.0 ") horn extension Horn Horn O.D.
Dimension drawings 12.2 Stainless steel threaded version Dimensions in mm (inch) Antenna Type Antenna O.D. 2 inch horn Height to sensor reference pointa) Measurement Range 1-1/2" threa‐ ded connec‐ tion 2" threaded con‐ nection 3" threaded con‐ nection 47.8 mm (1.88") N/A 166 mm (6.55") 180 mm (7.09") 20m (65.6 ft) 3 inch horn 74.8 mm (2.94") N/A 199 mm (7.85") 213 mm (8.39") 30m (98.4 ft) 4 inch horn 94.8 mm (3.73") N/A 254 mm (10") 268 mm (10.55") 30m (98.
Dimension drawings 12.3 Aluminum horn antenna 12.
Dimension drawings 12.4 Aluminum horn with polypropylene lens antenna and polymeric flange 12.
Dimension drawings 12.5 Aluminum horn antenna with aluminum aiming flange 12.
Dimension drawings 12.
Dimension drawings 12.
Dimension drawings 12.6 Universal stainless steel slotted flange 12.6 Universal stainless steel slotted flange Note Bolting and gasket materials The user is responsible for the selection of bolting and gasket materials which will fall within the limits of the flange and its intended use and which are suitable for the service conditions. r $ $ ① Number of slotted bolt holes ② Bolt hole circle max. diameter ③ Bolt hole circle min. diameter ④ flange O.D.
Dimension drawings 12.7 Universal polymeric flange 12.7 Universal polymeric flange r $ $ %&' ① ② ③ ④ Bolt hole circle max. diameter Bolt hole circle min. diameter Bolt hole Flange O.D. Nominal pipe size Flange O.D. Thickness Bolt hole cir‐ cle max. ∅ Bolt hole cir‐ cle min. Ø Bolt hole ra‐ dius No. of slot‐ ted holes 3 (80) 7.87 (200) 0.7 (17.5) 6.30 (160) 5.91 (150) 0.37 (9.5) 8 4 (100) 9.00 (229) 0.7 (17.5) 7.52 (191) 6.89 (175) 0.37 (9.
Dimension drawings 12.8 Universal aluminum aimer flange 12.8 Universal aluminum aimer flange Note Bolting and gasket materials The user is responsible for the selection of bolting and gasket materials which will fall within the limits of the flange and its intended use and which are suitable for the service conditions. "A" r "A" ① bolt hole circle max.
Dimension drawings 12.8 Universal aluminum aimer flange Pipe size Flange O.D. Thickness Bolt hole Bolt hole Bolt hole circle min Ø circle max Ø radius No. of slotted holes 3 (80) 7.87 (200) 0.88 (22.3) 6.30 (160) 5.91 (150) 0.37 (9.5) 8 4 (100) 9.00 (229) 0.88 (22.3) 7.52 (191) 6.89 (175) 0.37 (9.5) 8 6 (150) 11.22 (285) 0.88 (22.3) 9.53 (242) 9.45 (240) 0.45 (11.
Dimension drawings 12.9 Mounting bracket 12.9 Mounting bracket º [ ① ② ③ ④ Stainless steel socket head screw (4) M5 x 0.8 x 14 screws, washers, lock washers Mounting bracket (2) M5 x 0.8 x 16 screws, washers, lock washers (2) M5 x 0.
Dimension drawings 12.9 Mounting bracket Dimensions in mm (inch) Note Torque the bracket screws to 5 Nm (3.7ft/lbs) to hold the aiming adjustment of the antenna.
Application examples 13.1 13 Application Example Note In the applications illustrated below, values are for example purposes only. You can use this example as setup references. Enter the values in the parameter tables to select the corresponding functions. Configure the basic settings using the Quick Start wizard parameters. (These parameters are inter-related, and changes take effect only after you select YES in step 7 to apply changes.
Application examples 13.1 Application Example 7 5 6 4 3 1 2 ① ② ③ ④ ⑤ ⑥ ⑦ Level Low Calibration Point 16 m High Calibration Point Sensor Reference Point 0.5 m SITRANS LR260 To obtain level measurement/ 4 to 20 mA output proportional to flour levels: ● Low Calibration Pt. = vessel bottom ● High Calibration Pt.= 0.5 m from sensor reference point. ● Maximum fill/empty rate = 0.1 m/ min. ● In the event of a loss of echo, SITRANS LR260 is to go into Fail-safe High after two minutes.
Application examples 13.1 Application Example Parameter type Quick Start Wizard pa‐ rameters Independent parame‐ ters SITRANS LR260 with mA/HART Operating Instructions, 11/2019, A5E32337683-AD Parameter No. and Name Options/ Values Function Application Type (1.1.) (Page 74) STEEL Response Rate (1.2.) (Page 74) SLOW Slow = m/minute Units (1.3.) (Page 75) M meters Operation (1.4.) (Page 75) LEVEL Level Low Calibration Point (LOW CALIB. PT.) (1.5.
Application examples 13.
Appendix A: Technical reference A.1 A Appendix A: Tech Ref note Note Where a number follows the parameter name [for example, Master Reset (4.1.)] this is the parameter access number via the handheld programmer. See Parameter Reference (Page 73) for a complete list of parameters. A.2 Principles of operation SITRANS LR260 is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of liquids and slurries.
Appendix A: Technical reference A.3 Echo Processing Process intelligence provides high measurement reliability regardless of the dynamically changing conditions within the vessel being monitored. The embedded Process Intelligence dynamically adjusts to the constantly changing material surfaces within these vessels.
Appendix A: Technical reference A.3 Echo Processing A.3.3 Echo Lock If the echo selected by Algorithm is within the Echo Lock window, the window is centered about the echo, which is used to derive the measurement. ● Lock Off: SITRANS LR260 responds immediately to a new selected echo (within the restrictions set by the Maximum Fill / Empty Rate), but measurement reliability is affected. A.3.4 Echo Position Detection The echo position algorithm (2.2.4.1.2.
Appendix A: Technical reference A.3 Echo Processing Auto False Echo Suppression Range must be set to a distance shorter than the distance to the material level when the environment was learned, to avoid the material echo being screened out. Example before Auto False Echo Suppression 4 5 6 7 2 3URILOH >G%@ /HYHO GE 1 3 'LVWDQFH >P@ ① ② ③ ④ ⑤ ⑥ ⑦ default TVT false echo material echo high calibration point = 0 obstruction at 1.3. m material level at 3.
Appendix A: Technical reference A.5 Measurement Response A.4 Measurement Range A.4.1 Near Range Near Range programs (2.2.1.12) (Page 81) SITRANS LR260 to ignore the zone in front of the antenna. The default blanking distance is 50 mm (1.97 inch) from end of horn antenna. Near Range allows you to increase the blanking value from its factory default. Auto False Echo Suppression (2.2.5.2) (Page 87) is generally recommended in preference to extending the blanking distance from factory values. A.4.
Appendix A: Technical reference A.7 Damping A.6 mA Output The mA output is proportional to the level, in the range 4 to 20 mA. Generally, the output is set so that the output for 0% is 4 mA, and the output for 100% is 20 mA. 0 and 100% are percentages of the full-scale reading (m, cm, mm, ft, in).
Appendix A: Technical reference A.8 Loss of Echo (LOE) Damping example ① ② ③ ④ Level (m) Time (s) Input (level) Smoothed output ● time constant = 2 seconds ● input (level) change = 2 m ● In 5 time constants the output rises exponentially: from 63.2% of the change in the first time constant, to almost 100% of the change by the end of the 5th time constant. A.
Appendix A: Technical reference A.9 Fail-safe Mode A.9 Fail-safe Mode A.9.1 Fail-safe Mode The purpose of the Fail-safe setting is to put the process into a safe mode of operation in the event of a fault or failure. The value to be reported in the event of a fault is selected so that a loss of power or loss of signal triggers the same response as an unsafe level. A.9.2 Fail-safe Timer Fail-safe Timer determines the time to elapse after the last valid reading before a Failsafe state is activated.
Appendix A: Technical reference A.10 Process Pressure/Temperature derating curves A.10 Process Pressure/Temperature derating curves WARNING Exceeded maximum permissible operating pressure Danger of injury or poisoning. The maximum permissible operating pressure depends on the device version. The device can be damaged if the operating pressure is exceeded. Hot, toxic and corrosive process media could be released.
Appendix A: Technical reference A.12 Loop power Siemens Level Transmitters with flanged, threaded, or sanitary clamp type process mounts have no pressure-bearing housing of their own and, therefore, do not come under the Pressure Equipment Directive as pressure or safety accessories (see EU Commission Guideline A-08 and A-20). A.
Appendix A: Technical reference A.
Appendix A: Technical reference A.12 Loop power A.12.2 Allowable operating area of SITRANS LR260 Loop Voltage versus Loop Resistance 9 RKPV 5/ 9/ 9 RKPV 5/ 9/ 9 RKPV ① ② ③ ④ A.12.
Appendix A: Technical reference A.
Appendix A: Technical reference A.
Appendix B: HART Communications B.1 B HART communications Highway Addressable Remote Transducer, HART, is an industrial protocol that is superimposed on the 4-20 mA signal. It is an open standard, and full details about HART can be obtained from the HART Communication Foundation website: HART Communication Foundation (www.hartcomm.org) The radar device can be configured over the HART network using either the HART Communicator 375 by Fisher-Rosemount, or a software package.
Appendix B: HART Communications B.5 HART Communicator 375 Menu Structure B.5 HART Communicator 375 Menu Structure Note HART Communicator 375 is supported by SITRANS LR260 HART. The menu structure is aligned with the menu structure of SIMATIC PDM.
Appendix B: HART Communications B.
Appendix B: HART Communications B.7 Universal and Common Practice Commands B.6 Supported HART Commands SITRANS LR260 conforms to HART rev.
Product documentation and support C.1 C Product documentation Process instrumentation product documentation is available in the following formats: ● Certificates (http://www.siemens.com/processinstrumentation/certificates) ● Downloads (firmware, EDDs, software) (http://www.siemens.com/processinstrumentation/ downloads) ● Catalog and catalog sheets (http://www.siemens.com/processinstrumentation/catalogs) ● Manuals (http://www.siemens.
Product documentation and support C.2 Technical support C.2 Technical support Technical support If this documentation does not completely answer your technical questions, you can enter a Support Request (http://www.siemens.com/automation/support-request). Additional information on our technical support can be found at Technical Support (http:// www.siemens.com/automation/csi/service).
D List of abbreviations D.
List of abbreviations D.
LCD menu structure 14.1 14 LCD menu structure Note ● In Navigation mode, ARROW keys ( ) navigate the menu in the direction of the arrow. See Parameter Reference (Page 73) for detailed information and instructions. /(9(/ 0(7(5 48,&.
LCD menu structure 14.
LCD menu structure 14.1 LCD menu structure 6(59,&( '(9,&( 5(6(7 0$18) '$7( /&' )$67 02'( /&' &2175$67 32:(5(' +2856 32:(521 5(6(76 0(0 7(67 6(59,&( ,17(59$ 7,0( /$67 6(59 5(0$,1 /,)(7,0( 0$,17 5(4 /,0,7 0$,17 '(0 /,0,7 $/(57 $&7,9$7,21 6(59,&( ,17(59$/ 0$,17 67$7 $&. 67$786 $&.
LCD menu structure 14.
Glossary accuracy degree of conformity of a measure to a standard or a true value. algorithm a prescribed set of well-defined rules or processes for the solution of a problem in a finite number of steps. ambient temperature the temperature of the surrounding air that comes in contact with the enclosure of the device. antenna an aerial which sends out and receives a signal in a specific direction. There are four basic types of antenna in radar level measurement, horn, parabolic, rod, and waveguide.
Glossary blanking a blind zone extending away from the reference point plus any additional shield length.The instrument is programmed to ignore this zone. capacitance the property of a system of conductors and dielectrics that permits the storage of electricity when potential differences exist between the conductors. Its value is expressed as the ratio of a quantity of electricity to a potential difference, and the unit is a Farad. confidence Higher values represent higher quality.
Glossary Echo confidence describes the quality of an echo. Higher values represent higher quality. Echo threshold defines the minimum value required for an echo to be accepted as valid and evaluated. Echo Lock Window a window centered on an echo in order to locate and display the echo’s position and true reading. Echoes outside the window are not immediately processed. Echo Marker a marker that points to the processed echo. Echo Processing the process by which the radar unit determines echoes.
Glossary inductance the property of an electric circuit by virtue of which a varying current induces an electromotive force in that circuit or in a neighboring circuit. The unit is a Henry. microwaves the term for the electromagnetic frequencies occupying the portion of the radio frequency spectrum from 1 GHz to 300 GHz. multiple echoes secondary echoes that appear as double, triple, or quadruple echoes in the distance from the target echo.
Glossary radar radar is an acronym for RAdio Detection And Ranging. A device that radiates electromagnetic waves and utilizes the reflection of such waves from distant objects to determine their existence or position. range distance between a transmitter and a target. range extension the distance below the zero percent or empty point in a vessel.
Glossary TVT (time varying threshold) a time-varying curve that determines the threshold level above which echoes are determined to be valid. two wire radar a low-energy radar. Can be loop powered, analog, intrinsically safe 4 to 20 mA, or a digital (BUS) transmitter. waveguide antenna a hollow, metallic tube that transmits a microwave signal to the product target.
Index A Abbreviations and identifications list, 171 activating, 46 analog output fail signal, 126 select, 70 signal range, 126 simulate via PDM, 70 Auto False Echo Suppression explanation, 153 TVT Shaper adjustment, 67 C calibration schedules via PDM, 69 Catalog catalog sheets, 169 Certificates, 17, 169 Cleaning, 116 instructions, communication load, 126 maximum line length, 126 conduits requirements, 39 configuration Quick Start via LUI, 51 configuration flag reset, 70 Customer Support, (Refer to Technica
Index Modifications correct usage, 15 improper, 15 O operating principles cleaning, 151 P PDM see SIMATIC PDM, 59 PED (Pressure Equipment Directive), 160 performance specifications, 125 power, 125 power source requirements, 38 pressure applications Pressure Equipment Directive, 160 Process Intelligence, 151 programmer handheld, 50 programming adjust parameters via PDM, 64 via the handheld programmer, 51 Q Qualified personnel, 19 Quick Start Wizard via LUI, 51 via SIMATIC PDM, 60 R reading erratic troub