SITRANS LR260
To obtain level measurement/ 4 to 20 mA output proportional to flour levels:
Low Calibration Pt. = vessel bottom
High Calibration Pt.= 0.5 m from sensor reference point.
Maximum fill/empty rate = 0.1 m/ min.
In the event of a loss of echo, SITRANS LR260 is to go into Fail-safe High after two minutes.
Application examples