A5E03745453 - Non-incendive wiring (US/Canada only)
FM/CSA Class 1, Div 2 connection drawing number A5E03745541 can be downloaded from
the product page of our website at:
www.siemens.com/LR260.
Go to Technical Info > Images, graphics, drawings.
For power demands see Startup Behavior (Page 162).
The ATEX certificate listed on the nameplate.
The ATEX certificate listed on the nameplate can be downloaded from the product page of our
website at:
www.siemens.com/LR260.
Go to Support > Approvals / Certificates.
For power demands see Startup Behavior (Page 162).
For wiring requirements: follow local regulations.
Refer to Instructions specific to hazardous area installations (Page 41).
5.3.1.1 Special conditions for safe use (denoted by X after the certificate number)
Parts of the enclosure may be non-conducting and may generate an ignition-capable level
of electrostatic charge under certain extreme conditions. The user shall ensure that the
equipment is not installed in a location where it may be subjected to external conditions
(such as high-pressure steam), which might cause a build-up of electrostatic charge on non-
conducting surfaces.
Aluminium, magnesium, titanium or zirconium may be used at the accessible surface of the
equipment. In the event of rare incidents, ignition sources due to impact and friction sparks
could occur. This shall be considered when the Sitrans LR260 is being installed in locations
that specifically require Equipment Protection Level Ga or Da.
The equipment shall be bonded to the system earth in accordance with the relevant code of
practice.
Connecting
5.3 Hazardous area installation
SITRANS LR260 with mA/HART