Operating Instructions

Table Of Contents
6.2.3 Programming
6.2.3.1 Programming the radar device
Note
While the device is in PROGRAM mode the output remains fixed and does not respond to
changes in the device.
The device automatically returns to Measurement mode after a period of inactivity in
PROGRAM mode (between 15 seconds and 2 minutes, depending on the menu level).
6.2.3.2 Quick Start Wizard via the handheld programmer
Note
A reset to factory defaults should be performed before running the Quick Start Wizard if the
device has been used in a previous application. See Master Reset (4.1.).
The Quick Start wizard settings are inter-related and changes apply only after you
select Finish in the Wizard Complete step.
Do not use the Quick Start wizard to modify parameters: see instead Parameter Reference
(Page 73). (Perform customization for your application only after the Quick Start has been
completed).
Default settings in the parameter tables are indicated with an asterisk (*).
1. Quick Start
1.1. Quick Start Wiz
Point the programmer at the display from a maximum distance of 500 mm (1.6 ft), then
press RIGHT arrow to activate PROGRAM mode and open menu level 1.
Press RIGHT arrow twice to navigate to menu item 1.1 and open parameter view.
Press RIGHT arrow to open Edit mode or DOWN arrow to accept default values.
To change a setting, scroll to the desired item or key in a new value.
After modifying a value, press RIGHT arrow to accept it and press DOWN arrow to
move to the next item.
The Quick Start Wizard settings are inter-related and changes apply only after you click
on Yes in Apply? at the end of the Quick Start steps.
Commissioning
6.2 Local commissioning
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD 51