6.2.3.3 Application Type (1.1.)
Options STEEL Silo construction
CONCRETE
Default: STEEL
6.2.3.4 Response Rate (1.2.)
Sets the reaction speed of the device to measurement changes in the target range.
Options
SLOW 0.1 m/minute
MED 1.0 m/minute
FAST 10.0m/minute
Default: FAST
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy; faster settings allow for more level fluctuation.
6.2.3.5 Units (1.3.)
Select the units for the Quick Start variables (high and low calibration point, and level, distance,
or space).
Options M, CM, MM, FT, IN
Default: M
6.2.3.6 Operation (1.4.)
Options
NO SERVICE Stops updating measurements
and associated loop current.
Last valid measurement value is
displayed.
LEVEL Distance to material surface ref‐
erenced from Low Calibration
Point (process empty level).
SPACE Distance to material surface ref‐
erenced from High Calibration
Point (process full level).
DISTANCE Distance to material surface ref‐
erenced from Sensor Reference
Point.
Default: DISTANCE
Commissioning
6.2 Local commissioning
SITRANS LR260 with mA/HART
52 Operating Instructions, 11/2019, A5E32337683-AD