6.2.3.8 High Calibration Point (HIGH CALIB. PT.) (1.6.)
Distance from Sensor Reference to High Calibration Point: usually process full level.
(See Operation (Page 52) types for an illustration.)
Values Range: 0.0000 to 30.000 m
Default: 0.0 m
Related parameters Near Range (2.2.1.12.) (Page 81)
When setting the High Calibration Point value, note that echoes are ignored within Near Range
(2.2.1.12.) (Page 81)
6.2.3.9 Apply (1.7.)
In order to save the Quick Start settings, it is necessary to select Yes and apply changes.
Options
YES, NO, DONE
Display shows DONE when Quick Start is suc‐
cessfully completed.
Press Mode to return to Measurement mode.
6.2.3.10 Requesting an Echo Profile
Commissioning
6.2 Local commissioning
SITRANS LR260 with mA/HART
54 Operating Instructions, 11/2019, A5E32337683-AD